5P 750VA -1.5 KVA EU_EN
Installation and
user manual
5P750RC
5P1000RC
5P1500RC
Page 1

Advertisement

Table of Contents
loading

Summary of Contents for Eaton 5P1000RC

  • Page 1 Installation and user manual 5P750RC 5P1000RC 5P1500RC Copyright © 2015 EATON All rights reserved. 5P 750VA -1.5 KVA EU_EN Page 1...
  • Page 2: Special Symbols

    . IEC 62040-4: Environmental aspects - Requirements and reporting CE mark CE compliance contact: Eaton I.F. – 110 rue Blaise Pascal – 38330 Montbonnot Saint Martin - France The EC Declaration of Conformity is available upon request for products with a CE mark.
  • Page 3: Safety Of Persons

    During the replacement of the Battery Module, it is imperative to use the same type and number of element as the original Battery Module provided with the UPS to maintain an identical level of performance and safety. In case of doubt, don't hesitate to contact your EATON representative. Page 4...
  • Page 4: Table Of Contents

    1. Introduction ................. 5 1.1 Environmental protection ............. 5 2. Presentation ................. 6 2.1 Standard installations ..............6 2.2 Rear panel ................7 2.3 Control panel ................8 2.4 LCD description ................. 9 2.6 User settings ................10 3. Installation ................12 3.1 Unpacking and contents check .............
  • Page 5: Introduction

    Before installing your 5P, please read the booklet presenting the safety instructions. Then follow the indications in this manual. To discover the entire range of EATON products and the options available for the 5P range, we invite you to visit our web site at www.eaton.com/powerquality or contact your EATON representative.
  • Page 6: Presentation

    2. Presentation 2.1 Standard installations Rack model Description Weights Dimensions (mm/inch) (kg/lb) D x W x H 5P750RC 14.1/31.1 370*440*86.2 / 14.6*17.3*3.4 5P1000RC 15.0/33.1 370*440*86.2 / 14.6*17.3*3.4 5P1500RC 18.4/45.5 370*440*86.2 / 14.6*17.3*3.4 5P 750VA-1.5 KVA US_EN Page 6...
  • Page 7: Rear Panel

    2.2 Rear panel & & 5P750RC 5P1000RC 5P1500RC ① ③ ④ ② 1) Attached 1.8 m input power cord for AC power source 2) Slot for optional communication card 3) Primary group : Outlets for connection of critical equipment 4) Group 1: programmable outlets for...
  • Page 8: Control Panel

    2.3 Control panel The UPS has a five-button graphical LCD. It provides useful information about the UPS itself, load status, events, measurements and settings. 100% 19min 1EBM The following table shows the indicator status and description: Indicator Status Description The UPS is operating normally Green The UPS is on Battery mode.
  • Page 9: Lcd Description

    2.4 LCD description As default, or after 5 minutes of inactivity, the LCD displays the screen saver. The backlight LCD automatically dims after 10 minutes of inactivity. Press any button to restore the screen. The following table describes the status information provided by the UPS Note: If other indicator appears, see troubleshooting on section 5.1 for additional information.
  • Page 10: User Settings

    2.5 Display functions Press the Enter ) button to activate the menu options. Use the two middle buttons ( ) to scroll through the menu structure. Press the Enter ( ) button to select an option. Press the button to cancel or return to the previous menu.
  • Page 11 Submenu Available settings Default settings Cold start Enable [Disable] [Enable] Enables the product to be started on battery power. First cold start always disabled. Forced reboot Enable [Disable] [Enable] If mains recover during a shutdown sequence: - if enabled, shutdown sequence will complete and wait 10 seconds prior to restart - if disabled, shutdown sequence will...
  • Page 12: Installation

    3. Installation 3.1 Unpacking and contents check ⑨ ⑫ ⑬ ⑪ ⑩ (9) 5P UPS (10) Rail and wall mounting kits (11) Quick start, safety instructions and environmental document (12) RS232 communication cable (13) USB communication cable Packing materials must be disposed of in compliance with all local regulations concerning waste. Recycling symbols are printed on the packing materials to facilitate sorting.
  • Page 13: Battery Module Connection

    3.2 Battery module connection Caution: Before starting the UPS, please connect the internal battery. A. Remove the center panel ○ B. Remove the left-hand side of the front panel ○ C. Connect the battery module (never pull on the wires) ○...
  • Page 14: Rack Installation

    Follow steps 14 to 16 for model mounting on the rails. Use provided screws on step 15 of installation. Using a longer screw could present a safety risk. ⑮ ⑭ ⑮ ⑯ ⑯ ③ The rails and necessary hardware are supplied by EATON. 5P 750VA-1.5 KVA US_EN Page 14...
  • Page 15: Wall Mounting Of Rack Model

    3.4 Wall mounting of rack model Use provided screws on step 17 of installation. Using a longer screw could present a safety risk. ⑰ ⑱ ⑱ ⑰ Page 15 5P 750VA-1.5 KVA US_EN...
  • Page 16: Communication Ports

    USB (7) or RJ45 (6) communication ⑦ port on the UPS. ⑥ The UPS can now communicate with ⑬ EATON power management software. ⑫ It is not necessary to shut down the UPS before installing a communication Installation of the communication cards (optional) card 1.
  • Page 17: Operation

    4.1 Start-up and Normal operation To start the UPS: 1. Verify that the UPS power cord is plugged in. 2. The UPS front panel display illuminates and shows EATON logo. 3. Verify that the UPS status screen shows 4. Press the button on the UPS front panel for at least 2 seconds.
  • Page 18: Return Of Ac Input Power

    Low-battery warning • The indicator illuminates solid. • The audio alarm beeps every three seconds. The remaining battery power is low. Shut down all applications on the connected equipment because automatic UPS shutdown is imminent. End of battery backup time •...
  • Page 19: Maintenance

    5. Maintenance 5.1 Troubleshooting Operation status Possible cause Action If the condition persists, contact your The UPS does not recognize the internal batteries Batteries disconnected service representative The batteries are disconnected Verify that all batteries are properly connected. If the condition persists, contact your service representative.
  • Page 20: Battery-Module Replacement

    Mounting the new battery module Carry out the above instructions in reverse order. • To ensure safety and high performance, use only batteries supplied by EATON. • Take care to firmly press together the two parts of the connector during remounting.
  • Page 21: Appendices

    6. Appendices 6.1 Technical specifications Rack 5P750RC 5P1000RC 5P1500RC Output Power 750 VA 1000 VA 1440 VA @ 120 V 600 W 770 W 1100 W Output Power 625 VA 833VA 1080 VA @ 100 V 500 W 641W 825 W...
  • Page 22: Glossary

    6.2 Glossary Backup time Time during which the load can be supplied by the UPS operating on battery power. Battery test Internal UPS test to check battery status. Cold start The devices connected to the UPS can be started even if AC input power is not available.
  • Page 23 Page 23 www.eaton.com/Powerquality Eaton 5P 5P 750VA-1.5 KVA US_EN...