Low-battery warning
• The
and
• The audio alarm beeps every three seconds.
The remaining battery power is low. Shut down all applications on the connected equipment because
automatic UPS shutdown is imminent.
End of battery backup time
• LCD displays "End of backup time".
• All the LEDs go OFF .
• The audio alarms stops.

4.5 Return of AC Input Power

Following an outage, the UPS restarts automatically when AC input power returns (unless the restart
function has been disabled) and the load is supplied again.

4.6 UPS remote control functions

The 5P offers a choice between two remote control functions.
• RPO: Remote Power Off allow a remote contact to be used to disconnect all the equipment connected to
the UPS. Restarting the UPS requires manual intervention.
• ROO: Remote ON/OFF allows remote action of button
These functions are obtained by opening a contact connected between the appropriate pins of connector (4)
on the rear panel of the UPS (see figures below).
4
Remote control connection and test
1. Check that the UPS is OFF and disconnected from the AC input source.
2. Remove connector (4) after unscrewing the screws.
3. Connect a normally closed volt-free contact (60 V DC / 30 V AC max., 20 mA max., 0.75 mm
cross-section) between the two pins of connector (4) (see diagram).
4
4
4. Plug connector (4) into the back of the UPS.
5. Connect and restart the UPS following the previously described procedures.
6. Activate the external remote shutdown contact to test the function.
Warning. This connector must only be connected to SELV (Safety Extra-Low Voltage) circuits.
620-00082-02-i (en)
indicator illuminates solid.
Contact open: UPS shutdown
Contact closed: UPS start-up (UPS connected to AC power and AC power is available)
Note. The local ON/OFF control using button
Contact open: UPS shutdown, LED
To return to normal operation, deactivate the remote external contact and restart
the UPS by pressing button
to shut down the UPS.
overrides the remote-control function.
goes ON.
.
4. Operation
cable
2
Page 17