Electrical Input Connections; Electrical Output - Eaton 5PX Advanced User's Manual

Hide thumbs Also See for 5PX:
Table of Contents

Advertisement

Nominal frequency
Frequency range
Catalog Number
5PX1000IRT2UG2
5PX1500IRT2UG2
5PX2200IRT2UG2
5PX2200IRT3UG2
5PX3000IRT2UG2
5PX3000IRT3UG2

8.4 Electrical input connections

Catalog Number
Input connection
5PX1000IRT2UG2
IEC C14-10A
5PX1500IRT2UG2
5PX2200IRT2UG2
5PX2200IRT3UG2
IEC C20-16A
5PX3000IRT2UG2
5PX3000IRT3UG2

8.5 Electrical output

All models
Voltage regulation
Efficiency
Frequency regulation
Nominal output
Frequency
Output overload
614-40094-00
50/60Hz
47-70Hz
Default input
(Voltage/Current)
230V/10A
230V/10A
230V/16A
230V/16A
230V/16A
230V/16A
Input cable
Not provided
Schuko 16A to IEC320/16A
Normal mode
Boost : Vin*1.15
Buck : Vin*0.87
>96%
200/208/220/230/240V
Follows input frequency
[105%,120%] 30min
[120%,150%]5min
>150% 10S
Input nominal voltages
200-240V
Input voltage window
160-294V
adjustable to 150~294 
Battery mode
(-10% ,6%)
1000-2200 > 82%
3000 > 85%
+/-0.1 Hz
50/60Hz
[105% ~110%]  10s
[110%~150%]1s, 
>150% 0.15s