Eaton 5PX Advanced User's Manual page 22

Hide thumbs Also See for 5PX:
Table of Contents

Advertisement

Submenu
Restart batt.
level
Battery
charge mode
External
battery
Deep disch.
protect.
Input signals
Comm
settings
Outputs
signals
614-40094-00
Available settings
[0%] ... [100%]
Automatic restart will occur only when the set percentage
of battery charge is reached, and
and set to ON. A setting of 0% allows immediate automatic
restart when utility returns after a UPS shutdown due to
an extended power outage.
[ABM® cycling] [Constant charge]
[Auto detection] [Manual EBM set.] [Manual battery set.]
[Enabled] [Disabled]
If set to Enable, the UPS operates within the normal design
range of the battery during discharge.
If set to Disable, the UPS allows deeper battery discharge
to extend battery runtime at the expense of long-term
battery life (warranty is also void if set to disable).
[ROO] [RPO] [DB9-4]
Sets Input signals parameters (function, delay, operation)
through external contact connectors or RS232 port.
ROO port:
- [Function]: [No] [ROO] [RPO] [Building alarm][Shutdown
commands]
- [Delay]: [0s] ... [999s]
- [Active]: [Open] [Closed]
RPO port:
- [Function]: [No] [ROO] [RPO] [Building alarm][Shutdown
commands]
- [Delay]: [0s] ... [999s]
- [Active]: [Open] [Closed]
DB9-4 port:
- [Function]: [No] [ROO] [RPO] [Building alarm][Shutdown
Commands]
- [Delay]: [0s] ... [999s]
- [Active]: [Low] [High]:
[Relay] [DB9-1] [DB9-7] [DB9-8]
Sets events or fault that will actuate Output signal
parameters through external contact connector or RS232
port
[Relay]: [On bat] [Low bat] [Bat fault] [UPS OK] [Load
protected] [Load powered] [General alarm] [OVL pre-
alarm]
[DB9-1]: [On bat] [Low bat] [Bat fault] [UPS OK] [Load
protected] [Load powered] [General alarm] [OVL pre-
alarm]
"Auto
Restart" is enabled
Default settings
[0%]
[ABM® cycling]
[Auto detection]
Using standard EBM, UPS
automatically detects the
number of EBM connected
[Enable]
[No]
[0s]
[Closed]
[No]
[0s]
[Open]
[No]
[0s]
[High]
[Relay] : [Bat fault]
[DB9-1] : [Low bat]
[DB9-7] : [UPS OK]
[DB9-8] : [On bat]
22