Maintenance Schedule; Table 9. 30-Day, 6-Month And Annual Inspection And Maintenance - Eaton Power Xpert Solar 1500 User Manua

Utility-scale photovoltaic inverter
Table of Contents

Advertisement

Maintenance

Maintenance Schedule

Following the inverter's commissioning, the inverter must be
maintained on an appropriate schedule, fitting to the
installation. To establish the correct periodic maintenance
schedule, an initial check-list is provided in the table below.

Table 9. 30-Day, 6-Month and Annual Inspection and Maintenance

Field Maintenance
Tasks/Checks/Maintenance Log
Field-Wiring Connection Torque
PV DC Input Circuits
±PV Circuit
Equip. Grounds
AC Output Circuits
Phases A/B/C
Neutral (4-wire)
Ground
Inverter bolt-down fasteners
Air Filters and Passages
Inlets
Outlets
Overall Condition
Water Ingress
Conduit Seals
Cable/Wire glands
Control HMI
Cabinet
Transformer
Inverter Operation
Data Collection
Power Meter
Monitoring System
Expected Energy Harvest
Temperatures
Lose Cables
Evidence of "hot spots" at
Connections
AC Grid Connections
Labels (sun faded?)
Vandalism /Damage
Other as Specified
40
Power Xpert Solar 1500/1670 kW Inverter MN141001EN—October 2014 www.eaton.com
First
First
30 Days
6 Months
Annual
Comments
1) Record in Maintenance Log
2) Develop site-specific needs
3) Helpful recommendations
Based upon the initial 30-day and 6-month findings, develop and
schedule recurring (periodic) maintenance tasks to ensure proper
field-wiring torque.
After the initial 30-day and 6-month inspection:
Annual Inspection and checks of the inverter is required,
minimum.
Field wiring (PV and AC connection points)
Inverter
internal wiring and components
Filter-Capacitor inspection
Solar System external to the inverter
Inspect: Clean or Replace as Required
Excessive environmental dust that will require more periodic filter
checking and cleaning.
What is the cause of the filter dirt?
Local (temporary) construction or activity
Long-term (chronic) air contaminates
Increase periodic filter maintenance/change
Is there any undue water or moisture ingress?
Loss of seals
High (condensing) Humidity
Local flooding or Splash
Overall exterior condition
Overall Interior Condition
Has the Inverter performed as Expected?
If Not, Why?
Determine cause(s)
Inverter specific
Solar Site specific
– Modules
– Shading
– Soiling
Note for future maintenance