Eaton Power Xpert Solar 1500 User Manua page 84

Utility-scale photovoltaic inverter
Table of Contents

Advertisement

Appendix E
Table 23. Inverter Fuses, continued
Fuse
Purpose:
Designator
Cabinet
Circuit/Wire/Component Association
F61, F62
AC
48 Vdc Cabinet Fan1and Fan2
PS10+/TBF1: Circuit 18RD3311/3313 – F61
PS10+/TBF2: Circuit 18RD3314/3316 – F62
F63, F64
DC
DC Input Bus / VTB4 Voltage Sense Board
SS1+/VTB4-J1-1: Ckt 10RD208/209 – F63
SS1−/VTB4-J1-3: Ckt 10BK207/243 – F64
F65, F66, F67 DC
DC (PV) Voltage Sense Boards
See Fuses F10, F11, F12
F70, F72
AC
120 Vac Outlets (Plugs)
TB1-18/L-PLUG1: 14BU2018/2071 – F70
TB1-20/L-PLUG3: 14BU2020/2073 – F72
F74
CC
Line: 120 Vac Customer Loads TBC3-1/2/3
TB1-19 – 14BU2076 F74 – 14BU2077 – TBC3-1
F76, F77
AC
120 Vac cabinet FAN3 and FAN4
TR2-X1 - TB1-2 - 18RD2002 – F76 – 18RD2074
(DC CABINET) – TBF3 – FAN3
TR2-X3 - TB1-21: 18BU2021 – F77 – 18BU2075
(CONTROL CABINET) TBF4 – FAN4
F78, F79
LC
TR5 – Line Sync (relay)
F13-1/TR5-H1: 14RD4000 – F78 – 14RD4006
F14-1/TR5-H2: 14YL4001 – F79 – 14YL4007
F80, F81
LC
TR6 – Line Sync (relay)
F16-1/TR6-H1: 14RD4002 – F80 – 14RD4008
F17-1/TR6-H2: 14YL4003 – F81 – 14YL4009
F82, F83
LC
TR7 – Line Sync (relay)
F19-1/TR7-H1: 14RD4004 – F82 – 14RD4010
F20-1/TR7-H2: 14YL4005 – F83 – 14YL4011
FDC1–FDC24
DC
Input (PV) OCPD 'combiner' Fuses
Re-Combiner
Quantity 14–24
PV Fuses
2XL Amperage: 160/200/250/315/350/355
Amperage: 350/400/500/600/630
Note: 3L is different size fuse and holder
DC = DC Cabinet Section (PV Input Circuits)
AC = AC Control Power and AC Output Cabinet Section
LC = Inductor and Capacitor Cabinet Section (magnetics cabinet)
WTR = Cooling System Cabinet (Blower and Heat-Exchanger)
CC = Control Cabinet
74
Power Xpert Solar 1500/1670 kW Inverter MN141001EN—October 2014 www.eaton.com
Voltage
250 Vac
1000 Vdc
1000 Vdc
250 Vac
600 Vac
250 Vac
600 Vac
600 Vac
600 Vac
1000 Vdc
(based upon order/project)
Current
(A)
Manufacturer PN
2
SPT 5x20 0001.2507
1
PV-1A10F
1
PV-1A10F
15
FNQ-R-15
5
SPT 5x20 0001.2511
2
SPT 5x20 0001.2507
1
FNQ-R-1
1
FNQ-R-1
1
FNQ-R-1
160
PV-xxxA-2XL-B
(xxx = amperage)
200
B = Bladed
250
315
350
355
350
PV-xxxA-3L-B
to
630
Manufacturer
WTN PN
SCHURTER
44-4479
BUSSMANN
032-000800-0018
BUSSMANN
032-000800-0018
BUSSMANN
44-4481
SCHURTER
44-4480
SCHURTER
44-4479
BUSSMANN
032-000140-1091
BUSSMANN
032-000140-1091
BUSSMANN
032-000140-1091
BUSSMANN
160: 44-4504
200:44-4486
250: 44-4498
315: 44-4499
350: 44-4495
355: 44-4501
350: 44-4511
400: 44-4509
500: 44-4512
600: 44-4513
630: 44-4514