Eaton Power Xpert Solar 1500 User Manua page 47

Utility-scale photovoltaic inverter
Table of Contents

Advertisement

Wake-Up State
During the WAKEUP state the following conditions are
present:
The DC voltage is above the wake-up level
The AC line voltage and frequency are within the grid-tie
specified limits
This mode will last for approximately 10 seconds if the DC
voltage, AC voltage and frequency are within specifications
Power Xpert Solar 1500/1670 kW Inverter MN141001EN—October 2014 www.eaton.com
Power Export
During the power EXPORT state the following conditions are
present:
DC Voltage is within the MPPT operating range of the
inverter
AC Grid Voltage and frequency are within grid-tie
specification limits
The inverter stacks are synchronized with the AC line
(AC voltage waveform and frequency).
The solar array is supplying sufficient power to inverter
(typically greater than 7500 W)
Inverter Operation
37