Wake-Up State
During the WAKEUP state the following conditions are
present:
The DC voltage is above the wake-up level
●
The AC line voltage and frequency are within the grid-tie
●
specified limits
This mode will last for approximately 10 seconds if the DC
voltage, AC voltage and frequency are within specifications
Power Xpert Solar 1500/1670 kW Inverter MN141001EN—October 2014 www.eaton.com
Power Export
During the power EXPORT state the following conditions are
present:
DC Voltage is within the MPPT operating range of the
●
inverter
AC Grid Voltage and frequency are within grid-tie
●
specification limits
The inverter stacks are synchronized with the AC line
●
(AC voltage waveform and frequency).
The solar array is supplying sufficient power to inverter
●
(typically greater than 7500 W)
Inverter Operation