5
Power supply and batteries

External power supply PP2004

5.3 External power supply PP2004
64 | 121
The external power supply 'Merawex ZSP135 DR-7A-3 40 Ah' PP2004-A1 is a
wall-mounted power supply with batteries and the following connections:
230 V mains connection via power supply terminals
1x DC 24 V battery connection
2x DC 24 V supply outputs
Input for pre-assembled temperature sensor
2x plug connections for the supply system and battery monitoring signaling
function

Fig. 36: Wiring diagram for the batteries in the PP2004-A1

Ba
Battery separator, positive conductor
Battery +
Positive connection terminal DC 24 V
Battery -
Negative connection terminal DC 0 V
The battery connection cables must be as short as possible.
The positive and negative conductors must be routed together, either slightly
twisted or in a spiral cable.