6.3.7 Connect to call station
6.3.8 Connect to further PTO2008
A6V11940317_en--_a
The PTO2008-A1 provides two connectors ('X5' and 'RJ1') to connect the call
stations. 'RJ1' uses a copper Ethernet cable (CAT5) for the connection.
Call station connectors - 'X5' and 'RJ1'
Pin
Description
1
SO+
2
SO-
3
GND
4
D+
5
D-
6
DC 24 V
7
SI-
8
SI+
Table 44: PTO2008-A1 call station connectors - 'X5' and 'RJ1'
The PTO2008-A1 provides two connectors ('RJ2' and 'RJ3') to connect the
previous PTO2008-A1 to the next, with all necessary signals with copper Ethernet
cable (CAT5).
Call station connectors - 'RJ2' and 'RJ3'
Pin
Description
1
SO-
2
SO+
3
GND
4
D+
5
D-
6
DC 24 V
7
SI-
8
SI+
Table 45: PTO2008-A1 call station connectors - 'RJ2' and 'RJ3'
Install internal components
Call station interface (RS485) PTO2008-A1
Remark
Audio-Out +
Audio-Out -
GND
RS485 data +
RS485 data -
DC 24 V (with 500 mA fuse)
Audio-In -
Audio-In +
Remark
Audio-Out -
Audio-Out +
GND
RS485 data +
RS485 data -
DC 24 V
Audio-In -
Audio-In +
6