4
Mounting/Installation
Mount and install additional power amplifiers
4.7.2 Mount and install additional power amplifiers on
36 | 121
PC1002
Only the 'Power amplifier (1x500W)' PV1002-A1 can be mounted in the 'Voice
alarm panel Core 1000' PC1002-A2 cabinet. Other amplifier types are not allowed.
The power amplifiers PV1002-A1 are mounted in the amplifier mounting area. They
are connected to the audio matrix board in the amplifier connecting area. Up to 6
PV1002-A1 can be mounted in one PC1002-A2 cabinet.
NOTICE
Make sure that the 230 V and the batteries are both disconnected before the
power amplifiers PV1002-A1 are mounted.

Fig. 9: PC1002-A2 power amplifiers connection overview

To mount the power amplifier in the amplifier mounting area, the pre-assembled
power supply must be removed by following the steps below:
1. Disconnect all the wiring from the power supply.
2. Unscrew the 4 screws on the power supply.
3. Take out the power supply.
There are 2 amplifiers pre-mounted on position 'Amp 1' and 'Amp 2'. The additional
amplifiers are mounted on the selected position in the amplifier mounting area.