Sensata dimensions 12NP18 Owner's Manual page 37

Dc to ac power inverter/charger
Table of Contents

Advertisement

7-Seg Display Panel Messages Continued
Inverter Off Low Battery
The inverter is off due to a low battery voltage condition (≤10.5 volts for 5 seconds).
Inverter Off Overload
The inverter is off due to an overload condition or output short circuit.
NOTE: If the inverter/charger has been disabled by CAN, the "Inverter Off Overload" message will appear. If
using CAN with this system, check the inverter/charger LED blink code to verify cause.
Inverter Off High Temperature
The inverter is off due to a high temperature condition.
Inverter Off High Battery
The inverter is off due to a high charging voltage condition (>20 volts) and the display reports the value. The
inverter can tolerate up to 24 VDC for 5 minutes; if this condition continues for over 5 minutes, the unit will shut
down. Input voltages above 24 VDC will result in an immediate shutdown.
Charger Off High Temperature
The charger is off due to a high temperature condition.
Charger Off Battery Temperature
The charger is off due to a high battery temperature.
Charger Off Battery Problem
The charger may be off due to a shorted or open (missing) BTS.
Inverter Off Fault
The inverter is off due to a possible output short circuit or problem with inverter input.
Inverter Off Reverse Polarity
The inverter has detected that the battery is connected backwards. The inverter must be sent back to the factory for
evaluation.
Charger Off Battery Low Temp
The charger is off due to low battery temperature. Damage may occur to the battery if charging is continued.
Charger Off Overload
The charger is off due to posible short or DC load issue.
Page 37
12NP Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dimensions 12np20Dimensions 12np24Dimensions 12np30

Table of Contents