CONFIGURATIONS

Setting Configuration with Non-Volatile Memory (NVM) Setup Utility
The inverter/charger settings may be adjusted with a NVM Setup Utility kit which is sold separately. See the
Appendix for the part number of the kit. The kit consists of a Kvaser® CAN interface which connects to a USB
port on a laptop, a DB9 to RJ45 adapter, a terminating resistor, and a Windows PC program that can be installed on
a x32 or x64 machine. The laptop is not included with the purchase of the kit.
After the software has been properly installed, the Kvaser device may be plugged into the computer. The first time
the Kvaser is connected, the computer may need to download the appropriate Kvaser drivers from the Kvaser
website. Once the Kvaser device is ready to be used, the terminating resistor and DB9 to RJ45 adapter may be
connected to the inverter CAN port.
Once the inverter is turned on, the NVM Setup Utility may be opened on the laptop. The tool will automatically
look for a CAN device on the network. Once a unit is detected, it will automatically connect and display the current
settings.
NOTE: Only one CAN enabled inverter can be connected to the NVM Setup Utility at a time.
To make a settings change, click on a parameter and the available options will appear in a drop-down menu. Once
a setting is changed, the change is immediately set into the inverter's memory. After making all the settings changes,
it is necessary to turn the inverter off for 30 seconds and then turn it back on for the setting changes to take effect.
The settings may be saved to a configuration file. The configuration file may be used to program any additional
units that are to be programmed with the same settings.