11 Supplement
The status byte corresponds to profile 3.02 "Profibus PA Profile for Process Control Devices" coded.
The status "Measured value OK" is coded as 80 (hex) (Bit7 = 1, Bit6 ... 0 = 0).
The measured value is transferred as a 32 bit floating point number in the IEEE-754 format.
Byte n
Bit
Bit
Bit
Bit
Bit
Bit
Bit
4
7
6
5
3
2
2
VZ
2
7
2
6
5
2
4
2
3
Sign
Exponent
Bit
VZ
(Exponent - 127)
Value = (-1)
2
Fig. 39: Data format of the measured value
Coding of the status byte associated with the PA output value
You can find further information for the coding of the status byte in the Device Description 3.02 on
www.profibus.com.
Status code
0 x 00
0 x 04
0 x 0C
0 x 10
0 x 1f
0 x 44
0 x 48
0 x 4c
0 x 51
0 x 52
0 x 80
78
Byte n+1
Bit
Bit
Bit
Bit
Bit
Bit
0
4
1
7
6
5
3
2
2
2
0
2
2
-2
2
-3
2
-4
2
1
-1
Significant
(1 + Significant)
Description according to
Profibus standard
bad - non-specific
bad - configuration error
bad - sensor failure
bad - sensor failure
bad - out of service con-
stant
uncertain - last unstable
value
uncertain substitute set
uncertain - initial value
uncertain - sensor; con-
version not accurate - low
limited
uncertain - sensor; con-
version not accurate - high
limited
good (non-cascade) - OK
Byte n+2
Bit
Bit
Bit
Bit
Bit
Bit
Bit
4
7
6
5
0
2
1
2
2
-9
2
-10 -11 -12 -13 -14 -15 -16 -17
2
2
2
-6
2
-7
-8
-5
Significant
Possible cause
Flash-Update active
Adjustment error
Configuration error with PV-Scale (PV-Span too
small)
Unit irregularity
Error in the linearization table
Hardware error
Converter error
Leakage pulse error
Trigger error
Measured value generation error
Temperature measurement error
"Out of Service" mode switched on
Failsafe replacement value (Failsafe-Mode = "Last val-
ue" and already valid measured value since switching
on)
Switch on simulation
Failsafe replacement value (Failsafe-Mode = "Fsafe
value")
Failsafe replacement value (Failsafe-Mode = "Last valid
value" and no valid measured value since switching on)
Sensor value < lower limit
Sensor value > upper limit
OK
Bit
Bit
Bit
Bit
Bit
Bit
Bit
0
3
2
1
7
6
5
2
2
2
2
2
-18 -19 -20 -21 -22 -23
2
2
VEGAFLEX 82 • Profibus PA
Byte n+3
Bit
Bit
Bit
Bit
Bit
4
3
2
1
0
2
2
2
2
2
Significant