Vega VEGAFLEX 82 Operating Instructions Manual page 76

Tdr sensor for continuous level measurement of bulk solids
Hide thumbs Also See for VEGAFLEX 82:
Table of Contents

Advertisement

11 Supplement
dition to this manufacturer-specific GSD file, PNO also provides a general so-called profile-specific
GSD file. If the general GSD file is used, the sensor must be set to the profile-specific ident number
via the DTM software. By default, the sensor operates with the manufacturer-specific ID number.
When using the instruments on a segment coupler SK-2 or SK-3, no special GSD files are required.
VE010BF5
The following table shows the instrument ID and the GSD names for the VEGAFLEX sensor series.
Device name
VEGAFLEX 80 se-
ries
Cyclical data traffic
The master class 1 (e.g. PLC) cyclically reads out measured values from the sensor during opera-
tion. The below block diagram below shows which data can be accessed by the PLC.
Fig. 37: VEGAFLEX 82: Block diagram with AI FB 1 ... AI FB 3 OUT values
TB Transducer Block
FB 1 ... FB 3
Module of the PA sensors
For the cyclic data traffic, VEGAFLEX 82 provides the following modules:
AI FB1 (OUT)
– Out value of the AI FB1 after scaling
AI FB2 (OUT)
76
Instrument ID
VEGA
Instrument class in
profile 3.02
0xBF5
0x9702
Function Block
GSD file name
VEGA
Profile-specific
VE010BF5.GSD
PA139702.GSD
VEGAFLEX 82 • Profibus PA

Advertisement

Table of Contents
loading