Operating Instructions Manual as well as the Safety Manual that comes with instruments with SIL qualification. These manuals are available on our homepage. Operating instructions VEGAFLEX 82 - Four-wire 4 … 20 mA/ HART - Rod and cable probe: Document-ID 41830 Editing status of the quick setup guide: 2019-06-27...
During work on and with the device, the required personal protective equipment must always be worn. Appropriate use VEGAFLEX 82 is a sensor for continuous level measurement. You can find detailed information about the area of application in chapter "Product description". Operational reliability is ensured only if the instrument is properly used according to the specifications in the operating instructions manual as well as possible supplementary instructions.
That is why we have introduced an environment management system with the goal of continuously improving company environmental pro- tection. The environment management system is certified according to DIN EN ISO 14001. Please help us fulfil this obligation by observing the environmental instructions in this manual: • Chapter "Packaging, transport and storage" • Chapter "Disposal" VEGAFLEX 82 • Four-wire 4 … 20 mA/HART...
Move to "www.vega.com" and enter in the search field the serial number of your instrument. Alternatively, you can access the data via your smartphone: • Download the VEGA Tools app from the "Apple App Store" or the "Google Play Store" VEGAFLEX 82 • Four-wire 4 … 20 mA/HART...
Page 6
2 Product description • Scan the Data Matrix code on the type label of the instrument or • Enter the serial number manually in the app VEGAFLEX 82 • Four-wire 4 … 20 mA/HART...
Mounting instructions Installation position Mount VEGAFLEX 82 in such a way that the distance to vessel instal- lations or to the vessel wall is at least 300 mm (12 in). In non-metallic vessels, the distance to the vessel wall should be at least 500 mm (19.7 in).
Page 8
Fig. 3: Mounting in non-metallic vessel Flange Metal sheet Concrete vessel When mounting in thick concrete ceilings, VEGAFLEX 82 should be mounted front flush to the lower edge. In concrete silos, the distance to the wall should be at least 500 mm (20 in). VEGAFLEX 82 • Four-wire 4 … 20 mA/HART...
Page 9
In such cases, always carry out a false signal suppression after mounting. You can find further information under "Setup procedure". DN25 ... DN150 ≤ 150 mm (5.91") ≤ 100 mm (3.94") > DN150 ... DN200 Fig. 5: Mounting socket When welding the socket, make sure that the socket is flush with the vessel top. VEGAFLEX 82 • Four-wire 4 … 20 mA/HART...
5. Insert the wire ends into the terminals according to the wiring plan Information: Solid cores as well as flexible cores with wire end sleeves are insert- ed directly into the terminal openings. In case of flexible cores without end sleeves, press the terminal from above with a small screwdriver, the terminal opening is then free. When the screwdriver is released, the terminal closes again. VEGAFLEX 82 • Four-wire 4 … 20 mA/HART...
Polarity Voltage supply Voltage supply 4 … 20 mA output (active) 4 … 20 mA output (passive) Mass - output Function ground when in- stalling according to CSA (Canadian Standards Asso- ciation) VEGAFLEX 82 • Four-wire 4 … 20 mA/HART...
Page 13
Polarity Voltage supply Voltage supply 4 … 20 mA output (active) 4 … 20 mA output (passive) Mass - output Function ground when in- stalling according to CSA (Canadian Standards Asso- ciation) VEGAFLEX 82 • Four-wire 4 … 20 mA/HART...
Parameter adjustment - Quick setup Quick setup To quickly and easily adapt the sensor to the application, select the menu item "Quick setup" in the start graphic on the display and adjustment module. VEGAFLEX 82 • Four-wire 4 … 20 mA/HART...
Page 15
Corresponding linearisation curves are preprogrammed for these vessels. They represent the correlation between the level percentage and vessel volume. The linearization applies for the measured value indication and the current output. By activating the suitable curve, the percentage vessel volume is displayed correctly. VEGAFLEX 82 • Four-wire 4 … 20 mA/HART...
Page 16
5 Set up with the display and adjustment module VEGAFLEX 82 • Four-wire 4 … 20 mA/HART...
0.2 … 1.5 mm² (AWG 24 … 16) Voltage supply Operating voltage Ʋ Version for low voltage 9.6 … 48 V DC, 20 … 42 V AC, 50/60 Hz Ʋ Version for mains voltage 90 … 253 V AC, 50/60 Hz Reverse voltage protection Integrated Max. power consumption 4 VA; 2.1 W VEGAFLEX 82 • Four-wire 4 … 20 mA/HART...