Datcon DT9002 Operating Instructions Manual page 81

Intrinsically safe process indicator
Table of Contents

Advertisement

DT9002
20180621-V1
Example for the practical usage of the limit outputs
There is a 100-litre tank, whose liquid level is indicated by
the instrument DT9002 in 0-100 litres, without decimals.
Task:
The limit output No.1 should control a pump, that switches
ON when the liquid-level goes lower than 70 litres, and
switches OFF when it goes higher than 90 litres.
The limit output No.2 should control a buzzer. The buzzer
should be signalling continuously as long as a manual
acknowledgement takes place, in those cases when the
liquid level goes, at any time, lower than 50 litres, or when it
goes higher than 95 litres.
The settings of the limit outputs are as follows:

operating mode=
liquid level is lower than the low limit)

Low limit =

Hysteresis of the low limit =

High limit =

Hysteresis of the high limit =
indifferent)

Alarm mode =

Operating mode=
liquid level does not fall between the limits.)

Low limit =

Hysteresis of the low limit =

High limit =

Hysteresis of the high limit =

Alarm mode =

(Switches ON, when the



(it's value is indifferent)


(Switches ON, when the



(it's value is
81

Advertisement

Table of Contents
loading

Table of Contents