TP48200A-HT19C3 and TP48200A-HT19C4 Telecom
Power
User Manual
Item
Voltage measurement range
Continuous overload voltage
Current measurement range
Single phase power measurement range
Total power measurement range
Frequency measurement range
Power factor measurement range
Current precision
Voltage precision
Power precision
Power factor precision
Frequency precision
Electric energy precision
Operating temperature
Storage temperature
Relative humidity
Power input
Power consumption
Issue 03 (2019-11-15)
Specifications
800 V AC
200 mA to 100 A
0-48000 W/var/VA
0-96000 W/var/VA
45-60 Hz
-1 to 1
0.5% (10-100 A)
0.5% (20-400 V); line voltage: 1.0%
1.0%
1.0%
45-60 Hz
1.0% (0.5 C-1-0.5 L)
-10° C to +50° C
-25° C to +75° C
20%-95% RH (non-condensing)
2 W
Copyright © Huawei Technologies Co., Ltd.
Line voltage: 30-600 V AC
Phase voltage: 20-400 V AC
18-90 V DC
Two options: 85-265 V AC or 85-330 V DC
A Technical Specifications
87