Danfoss VLT AQUA Drive FC 202 Operating Manual page 70

110–400 kw
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Specifications
Analog output
Number of programmable analog outputs
Terminal number
Current range at analog output
Maximum resistor load to common at analog output
Accuracy on analog output
Resolution on analog output
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, RS485 serial communication
Terminal number
Terminal number 61
The RS485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from the
supply voltage (PELV).
Digital output
Programmable digital/pulse outputs
Terminal number
Voltage level at digital/frequency output
Maximum output current (sink or source)
Maximum load at frequency output
8
8
Maximum capacitive load at frequency output
Minimum output frequency at frequency output
Maximum output frequency at frequency output
Accuracy of frequency output
Resolution of frequency outputs
1) Terminals 27 and 29 can also be programmed as inputs.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, 24 V DC output
Terminal number
Maximum load
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
Relay outputs
Programmable relay outputs
Relay 01 terminal number
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
Maximum terminal load (DC-13)
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
Maximum terminal load (DC-13)
Minimum terminal load on 1–3 (NC), 1–2 (NO)
Environment according to EN 60664-1
Relay 02 terminal number
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
Maximum terminal load (DC-13)
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
68
®
VLT
AQUA Drive FC 202
1)
on 1–2 (NO) (Resistive load)
on 1–2 (NO) (Inductive load @ cosφ 0.4)
1)
1)
on 1–2 (NO) (Resistive load)
1)
on 1–2 (NO) (Inductive load)
1)
on 1–3 (NC) (Resistive load)
on 1–3 (NC) (Inductive load @ cosφ 0.4)
1)
1)
on 1–3 (NC) (Resistive load)
1)
on 1–3 (NC) (Inductive load)
1)
on 4–5 (NO) (Resistive load)
on 4–5 (NO) (Inductive load @ cosφ 0.4)
1)
1)
on 4–5 (NO) (Resistive load)
1)
on 4–5 (NO) (Inductive load)
1)
on 4–6 (NC) (Resistive load)
on 4–6 (NC) (Inductive load @ cosφ 0.4)
1)
Danfoss A/S © 11/2016 All rights reserved.
2)3)
Overvoltage category III/pollution degree 2
2)3)
0/4-20 mA
500 Ω
Maximum error: 0.8% of full scale
8 bit
68 (P, TX+, RX+), 69 (N, TX-, RX-)
Common for terminals 68 and 69
27, 29
0–24 V
40 mA
1 kΩ
10 nF
0 Hz
32 kHz
Maximum error: 0.1% of full scale
12 bit
12, 13
200 mA
1–3 (break), 1–2 (make)
400 V AC, 2 A
240 V AC, 0.2 A
80 V DC, 2 A
24 V DC, 0.1 A
240 V AC, 2 A
240 V AC, 0.2 A
50 V DC, 2 A
24 V DC, 0.1 A
24 V DC 10 mA, 24 V AC 2 mA
4–6 (break), 4–5 (make)
400 V AC, 2 A
240 V AC, 0.2 A
80 V DC, 2 A
24 V DC, 0.1 A
240 V AC, 2 A
240 V AC, 0.2 A
MG21A402
1
42
2
1)
2