Danfoss VLT AQUA Drive FC 202 Operating Manual page 58

110–400 kw
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Maintenance, Diagnostics, a...
Number
Text
1794
Power data not transferred correctly at power-up
to the digital signal processor.
1795
The digital signal processor has received too many
unknown SPI telegrams. The frequency converter
also uses this fault code if the MCO does not
power up correctly. This situation can occur due to
poor EMC protection or improper grounding.
1796
RAM copy error.
2561
Replace the control card.
2820
LCP stack overflow.
2821
Serial port overflow.
2822
USB port overflow.
3072–5122
Parameter value is outside its limits.
5123
Option in slot A: Hardware incompatible with the
control board hardware.
5124
Option in slot B: Hardware incompatible with the
7
7
control board hardware.
5125
Option in slot C0: Hardware incompatible with the
control board hardware.
5126
Option in slot C1: Hardware incompatible with the
control board hardware.
5376–6231
Internal fault. Contact the Danfoss supplier or
Danfoss service department.
Table 7.4 Internal Fault Codes
ALARM 39, Heat sink sensor
No feedback from the heat sink temperature sensor.
The signal from the IGBT thermal sensor is not available on
the power card. The problem could be on the power card,
on the gatedrive card, or the ribbon cable between the
power card and gatedrive card.
WARNING 40, Overload of digital output terminal 27
Check the load connected to terminal 27 or remove the
short circuit connection. Check parameter 5-00 Digital I/O
Mode and parameter 5-01 Terminal 27 Mode.
WARNING 41, Overload of digital output terminal 29
Check the load connected to terminal 29 or remove the
short-circuit connection. Also check parameter 5-00 Digital
I/O Mode and parameter 5-02 Terminal 29 Mode.
WARNING 42, Overload of digital output on X30/6 or
overload of digital output on X30/7
For terminal X30/6, check the load connected to terminal
X30/6 or remove the short -circuit connection. Also check
parameter 5-32 Term X30/6 Digi Out (MCB 101) (VLT
General Purpose I/O MCB 101).
For terminal X30/7, check the load connected to terminal
X30/7 or remove the short-circuit connection. Check
parameter 5-33 Term X30/7 Digi Out (MCB 101) (VLT
General Purpose I/O MCB 101).
ALARM 43, Ext. supply
®
VLT
Extended Relay Option MCB 113 is mounted without
external 24 V DC. Either connect a 24 V DC external supply
or specify that no external supply is used via
56
®
VLT
AQUA Drive FC 202
parameter 14-80 Option Supplied by External 24VDC, [0] No.
A change in parameter 14-80 Option Supplied by External
24VDC requires a power cycle.
ALARM 45, Earth fault 2
Ground fault.
Troubleshooting
ALARM 46, Power card supply
The supply on the power card is out of range.
There are 3 supplies generated by the switch mode supply
(SMPS) on the power card:
When powered with VLT
the 24 V and 5 V supplies are monitored. When powered
with 3-phase mains voltage, all 3 supplies are monitored.
Troubleshooting
WARNING 47, 24 V supply low
The supply on the power card is out of range.
There are 3 supplies generated by the switch mode supply
(SMPS) on the power card:
Troubleshooting
WARNING 48, 1.8 V supply low
The 1.8 V DC supply used on the control card is outside of
the allowable limits. The supply is measured on the control
card.
®
Troubleshooting
®
WARNING 49, Speed limit
The warning is shown when the speed is outside of the
specified range in parameter 4-11 Motor Speed Low Limit
[RPM] and parameter 4-13 Motor Speed High Limit [RPM].
When the speed is below the specified limit in
Danfoss A/S © 11/2016 All rights reserved.
Check for proper grounding and loose
connections.
Check for proper wire size.
Check the motor cables for short circuits or
leakage currents.
24 V.
5 V.
±18 V.
®
24 V DC Supply MCB 107, only
Check for a defective power card.
Check for a defective control card.
Check for a defective option card.
If a 24 V DC supply is used, verify proper supply
power.
24 V.
5 V.
±18 V.
Check for a defective power card.
Check for a defective control card.
If an option card is present, check for
overvoltage.
MG21A402