Danfoss VLT AQUA Drive FC 202 Operating Manual page 66

110–400 kw
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Specifications
High/normal load*
Typical shaft output at 550 V [kW]
Typical shaft output at 575 V [hp]
Typical shaft output at 690 V [kW]
Enclosure IP20
Enclosure IP21/IP54
Output current
Continuous (at 550 V) [A]
Intermittent (60 s overload) (at 550 V)[A]
Continuous (at 575/690 V) [A]
Intermittent (60 s overload) (at 575/690 V)
[kVA]
Continuous kVA (at 550 V) [kVA]
Continuous kVA (at 575 V) [kVA]
Continuous kVA (at 690 V) [kVA]
Maximum input current
Continuous (at 550 V) [A]
Continuous (at 575 V) [A]
Continuous (at 690 V) [A]
8
8
Maximum cable size
Mains, motor, brake, and load share
2
2)
(mm
/AWG
)
Maximum external mains fuses [A]
Estimated power loss at 575 V [W]
Estimated power loss at 690 V [W]
Weight, enclosure, IP20/IP21/IP54, [kg (lbs)]
4)
Efficiency
Output frequency [Hz]
Heat sink overtemperature trip [°C (°F)]
Power card ambient trip [°C (°F)]
*High overload=150% current for 60 s, Normal overload=110% current for 60 s.
Table 8.3 Technical Specifications, D2h/D4h, Mains Supply 3x525–690 V AC
1) For type of fuse, consult the operating instructions.
2) American Wire Gauge.
3) The typical power loss is at normal conditions and expected to be within
These values are based on a typical motor efficiency (IE2/IE3 border line). Lower efficiency motors add to the power loss in the frequency converter
and the opposite is also true. Applies to dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting,
the power losses may increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer
to www.danfoss.com/vltenergyefficiency. Further options and customer load can add up to 30 W to the losses (though typically only 4 W extra for
a fully loaded control card or options for slot A or slot B, each).
4) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency.
Efficiency measured at nominal current. For energy efficiency class, see chapter 8.4.1 Ambient Conditions. For part load losses, see
www.danfoss.com/vltenergyefficiency.
Enclosure size
D5h
D6h
D7h
D8h
Table 8.4 D5h–D8h Weight
64
®
VLT
AQUA Drive FC 202
N200
HO
NO
132
160
200
250
160
200
201
253
302
278
192
242
288
266
191
241
191
241
229
289
198
245
189
234
197
240
3)
2361
3074
2446
3175
3)
Description
D1h ratings+disconnect and/or brake chopper
D1h ratings+contactor and/or circuit breaker
D2h ratings+disconnect and/or brake chopper
D2h ratings+contactor and/or circuit breaker
Danfoss A/S © 11/2016 All rights reserved.
N250
N315
HO
NO
HO
160
200
200
250
300
300
200
250
250
D4h
D2h
253
303
303
380
333
455
242
290
290
363
319
435
241
289
289
241
289
289
289
347
347
245
299
299
234
286
286
240
296
296
2x185 (2x350 mcm)
550
3012
3723
3642
3123
3851
3771
125 [275]
0.98
0–590
110 (230)
80 (176)
± 15% (tolerance relates to variety in voltage and cable conditions.)
Maximum weight, [kg (lbs)]
166 (255)
129 (285)
200 (440)
225 (496)
P400
NO
HO
NO
250
250
315
350
350
400
315
315
400
360
360
418
396
540
460
344
344
400
378
516
440
343
343
398
343
343
398
411
411
478
355
355
408
339
339
390
352
352
400
4465
4146
5028
4614
4258
5155
0–525
MG21A402