Technical Details; Control Panel - DEGA UDA III User Manual

Gas detection control panel
Table of Contents

Advertisement

2 Technical details

Control panel

Power voltage:
Transmitter connection cable:
via HART (4-20 mA)
(only with DEGA UDA III AI8 card)
via RS485:
Sensor connection cable:
DEGA Tc II temperature sensor:
Flood sensor DEGA Zc II:
Cable for signaling and button connection
Output:
RS485 communication speed:
Functional safety EN61508:
Dimensions without bushings
Weight:
Internal memory capacity:
Memory storage interval:
Maximum number of transmitters:
Digital lines:
Topology of connected transmitters:
Maximum number of transmitters on the bus: 32
Maximum cross-section of wires to the terminal board:
Other inputs:
Logic levels of digital input:
230 V AC / max 150 W
24 V DC / 6.3 A nominal, functional range 20-28 V
shielded cable 3 x 1 mm (max. 1200 m) or 3 x 1.5 mm (max. 2400 m)
shielded cable 4 x 0.8 mm (max. 1200 m)
shielded cable 4 x 1.5 mm (max. 1200 m)
shielded cable 3 x 0.25 mm (max. 100 m)
shielded cable 4 x 0.25 mm (max. 100 m)
2 x 1 mm
20x switching relay 250 V/10 A
2x output for sound and optical signaling (max. 24V/5A)
LTE modem
- sending SMS messages
-
transfer of measured data to the cloud
Ethernet
- sending emails (in development)
-
transfer of measured data to DegaVisioIII
RS485_HOST
- MODBUS for control system
RS485_HOST
- DEGA protocol
USB
- for configuration of the control panel via PC
9.6 kB
SIL 1
460 mm x 320 mm x 120 mm (WxHxD)
4.5 kg
300 days at a recording interval of 30 s
30 s (adjustable range 30-255 s)
200
8
Bus (BUS) - 8 independent buses
Circular (LOOP) - 4 independent circuits
2.5 mm
2
DEGA Tc II (critical temperature sensor)
DEGA TL II (acoustic signaling release button)
2x digital input for general use
0-1V - log 0
2-28V - log 1
8

Advertisement

Table of Contents
loading

Table of Contents