Channel Status - DEGA UDA III User Manual

Gas detection control panel
Table of Contents

Advertisement

6.6.1

Channel status

The status of the channel is indicated by the color background of the channel graphics and the graphic appearance of the
channel element. The following table describes the individual states and how they are indicated. This is an overview
information, details can be obtained by clicking on the channel and displaying the channel details screen.
State
Graphic
Design
Ok
Initialization
Glow
Disorder
Alarm 1
Alarm 2
Alarm 3
Alarm 4
PEL/STEL
alarm
Calibration
Inactive
Table 9 Possible channel states
Indication
Description
White
Functional channel.
background and
green check
Gray background
Initialization of communication with the transmitter. The control panel
and inscription
tries to establish communication and configure the transmitter. In case
'initialization'
of failure, the channel status changes to Fault.
Inscription
The transmitter sensor glows when the power is turned on. The
'heating' instead
transmitter waits for the values from the transmitter to stabilize. After
of value
stabilization, it switches itself to the measurement mode.
Yellow
Channel error. The basic error status is displayed in the channel
background
description. The detailed information about the error can be obtained
in the channel details screen and in the control panel log.
Value indicator
Alarm 1 is indicated by the color of the value indicator and the A1
mark.
Value indicator
Alarm 2 is indicated by the color of the value indicator and the A2
mark.
Value indicator
Alarm 3 is indicated by the color of the value indicator and the A3
mark.
Value indicator
Alarm 4 is displayed by the color of the value indicator, the A4 mark
and red
and the change of the color background of the channel to red.
background
Condition - blue
The PEL/STEL channel alarm is indicated by a flashing blue triangle in
triangle
the lower right corner. The detailed information about active alarms
can be obtained in the channel details screen.
Condition -
Passed transmitter calibration.
calibration mark
Gray background
Blocked channel. For service and maintenance purposes, the channels
and inscription
can be blocked in the control panel settings. Attention, resetting the
'inactive'
control panel will unblock all channels.
40

Advertisement

Table of Contents
loading

Table of Contents