6.11.1 Control panel settings

The dialog is used to set general parameters and functions of the control panel.
Dialog item
Device name
External temperature sensor
UPS
SD card
Sort channels by error condition
Negative temperature display
Syslog
Time setting
Change Password
Format SD
Password reset
Control panel reset
Table 18 Control panel settings
Figure 41 Control panel settings
Description
Control panel description
External control panel temperature sensor - enable / set
UPS power supply - enable / set
Enables the use of an SD card to store the history of values. If
the function is disabled, the history is stored in the internal
RAM (only a few hours / reset clears the history).
When using an SD card, the history is stored approximately 1
year back.
Channel sorting method (by status / by channel number) on the
main screen.
Displaying a negative channel value. Some transmitters send a
negative concentration value (e.g. in case of incorrect zero
calibration), the control panel ignores the negative value and
displays only 0. The setting can also enable the display of
negative values sent by the transmitter.
Viewing the system log
Control panel time setting
Dialog for changing the password of the logged in user
Reformats the SD card with the FAT32 file system - clears the
history of values / events
Reset all users' passwords to default values
Performs a device reset