Toshiba MMD-AP0724H2UL Service Manual page 77

High static ducted type
Hide thumbs Also See for MMD-AP0724H2UL:
Table of Contents

Advertisement

Procedure 2: replacing P.C. board
1
Replace the faulty P.C. board with a service P.C. board.
Be sure to replicate the old jumper setting (removal), and connector short-circuit setting (e.g. CN34) on the
service P.C. board. (See the diagram at below.)
2
It is necessary to establish a one-to-one correspondence between the indoor unit being serviced
and the remote controller.
Turn on the indoor unit using one of the methods described below according to the system configuration.
(1) Single (stand-alone) operation
Turn on the indoor unit and proceed to Procedure 3.
(2) Group operation
A) If it is possible to selectively turn on the indoor unit being serviced
Turn on the indoor unit being serviced and proceed to Procedure 3.
B) If it is not possible to selectively turn on the indoor unit being serviced (Case 1)
a) Temporarily disconnect the group control wiring from terminals A and B of the indoor unit being serviced.
b) Connect the remote controller wiring to the terminals, turn on the indoor unit, and proceed to Procedure 3.
* If this method cannot be used, proceed to the alternative method described below (Case 2).
C) If it is not possible to selectively turn on the indoor unit being serviced (Case 2)
a) Remove the CN41 connectors of all other indoor units in the same group.
b) Turn on the indoor unit and proceed to Procedure 3.
Case 1
Indoor unit
Case 2
Indoor unit
Remove CN41
connectors of all
other indoor units
in same group.
* Be sure to restore the temporarily removed group control wiring and CN41 connectors to their initial states
after Procedure 3 has been completed.
All manuals and user guides at all-guides.com
(MCC-1403)
CN030
If a short-circuiting plug had been used on the replaced
P.C. board, reuse it on the service P.C. board.
Indoor unit
P.C. board
P.C. board
Group control wiring
Indoor unit
Indoor unit (one being serviced)
P.C. board
P.C. board
Group control wiring
– 77 –
CN041
Indoor unit (one being serviced)
Service P.C. board
Remove group control wiring from terminals
A and B of indoor unit being serviced, and
connect remote controller wiring.
Remote controller
Service P.C. board
Remote controller

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmd-ap0964h2ul

Table of Contents