Toshiba MMD-AP0724H2UL Service Manual page 62

High static ducted type
Hide thumbs Also See for MMD-AP0724H2UL:
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
controller
Check code
Sub-code
H07
H07
01: TK1 sensor
error
02: TK2 sensor
error
03: TK3 sensor
error
04: TK4 sensor
error
05: TK5 sensor
error
H08
H08
H15
H15
All manuals and user guides at all-guides.com
Location
of
Description
System status
detection
I/F
Low oil level
All stop
protection
I/F
Error in
All stop
temperature
sensor for oil
level detection
All stop
All stop
All stop
All stop
I/F
TD2 sensor
All stop
miswiring
(incomplete
insertion)
– 62 –
Error detection
Check items (locations)
condition(s)
Operating compressor
<All outdoor units in
detects continuous state of
corresponding line to be
low oil level for about 2 hours.
checked>
• Check balance pipe
service valve to confirm full
opening.
• Check connection and
installation of TK1, TK2,
TK3, TK4, and TK5
sensors.
• Check resistance
characteristics of TK1,
TK2, TK3, TK4, and TK5
sensors.
• Check for gas or oil leak in
same line.
• Check for refrigerant
entrapment inside
compressor casing.
• Check SV3A, SV3B,
SV3C, SV3D, SV3E, and
SV3F valves for defect.
• Check oil return circuit of
oil separator for clogging.
• Check oil equalizing circuit
for clogging.
Sensor resistance is infinity
• Check connection of TK1
or zero (open/short circuit).
sensor connector.
• Check resistance
characteristics of TK1
sensor.
• Check for defect in outdoor
P.C. board (I/F).
Sensor resistance is infinity
• Check connection of TK2
or zero (open/short circuit).
sensor connector.
• Check resistance
characteristics of TK2
sensor.
• Check for defect in outdoor
P.C. board (I/F).
Sensor resistance is infinity
• Check connection of TK3
or zero (open/short circuit).
sensor connector.
• Check resistance
characteristics of TK3
sensor.
• Check for defect in outdoor
P.C. board (I/F).
Sensor resistance is infinity
• Check connection of TK4
or zero (open/short circuit).
sensor connector.
• Check resistance
characteristics of TK4
sensor.
• Check for defect in outdoor
P.C. board (I/F).
Sensor resistance is infinity
• Check connection of TK5
or zero (open/short circuit).
sensor connector.
• Check resistance
characteristics of TK5
sensor.
• Check for defect in outdoor
P.C. board (I/F).
Air discharge temperature of
• Check installation of TD2
(TD2) does not increase
sensor.
despite compressor 2 being
• Check connection of TD2
in operation.
sensor connector and
wiring.
• Check resistance
characteristics of TD2
sensor.
• Check for defect in outdoor
P.C. board (I/F).