Check code
Outdoor 7-segment display
Main
remote
Check code
controller
Sub-code
01: TK1 oil
circuit error
02: TK2 oil
circuit error
03: TK3 oil
circuit error
04: TK4 oil
circuit error
05: TK5 oil
circuit error
H16
H16
H25
H25
All manuals and user guides at all-guides.com
Location
System
of
Description
status
detection
I/F
Oil level
All stop
detection
circuit error
I/F
TD3 sensor
All stop
miswiring
(incomplete
insertion)
– 63 –
Error detection
Check items (locations)
condition(s)
No temperature
• Check for disconnection of TK1 sensor.
change is detected
• Check resistance characteristics of
by TK1 despite
TK1 sensor.
compressor 1 having
• Check for connection error involving
been started.
TK1, TK2, TK3, TK4, and TK5 sensors
• Check for faulty operation in SV3E or
SV3F valve.
• Check for clogging in oil equalizing
circuit capillary and faulty operation in
check valve.
• Check for refrigerant entrapment inside
compressor.
No temperature
• Check for disconnection of TK2 sensor.
change is detected
• Check resistance characteristics of
by TK2 despite
TK2 sensor.
compressor 2 having
• Check for connection error involving
been started.
TK1, TK2, TK3, TK4, and TK5 sensors
• Check for faulty operation in SV3E or
SV3F valve.
• Check for clogging in oil equalizing
circuit capillary and faulty operation in
check valve.
• Check for refrigerant entrapment inside
compressor.
No temperature
• Check for disconnection of TK3 sensor.
change is detected
• Check resistance characteristics of
by TK3 despite
TK3 sensor.
compressor 3 having
• Check for connection error involving
been started.
TK1, TK2, TK3, TK4, and TK5 sensors
• Check for faulty operation in SV3E or
SV3F valve.
• Check for clogging in oil equalizing
circuit capillary and faulty operation in
check valve.
• Check for refrigerant entrapment inside
compressor.
No temperature
• Check for disconnection of TK4 sensor.
change is detected
• Check resistance characteristics of
by TK4 despite
TK4 sensor.
compressor having
• Check for connection error involving
been started.
TK1, TK2, TK3, TK4, and TK5 sensors
• Check for faulty operation in SV3E or
SV3F valve.
• Check for clogging in oil equalizing
circuit capillary and faulty operation in
check valve.
• Check for refrigerant entrapment inside
compressor.
No temperature
• Check for disconnection of TK5 sensor.
change is detected
• Check resistance characteristics of
by TK5 despite
TK5 sensor.
compressor having
• Check for connection error involving
been started.
TK1, TK2, TK3, TK4, and TK5 sensors
• Check for faulty operation in SV3E
valve.
• Check for clogging in oil equalizing
circuit capillary and faulty operation in
check valve.
• Check for refrigerant entrapment inside
compressor.
Air discharge
• Check installation of TD3 sensor.
temperature (TD3)
• Check connection of TD3 sensor
does not increase
connector and wiring.
despite compressor
• Check resistance characteristics of
3 being in operation.
TD3 sensor.
• Check for defect in outdoor P.C. board
(I/F).