Toshiba MMD-AP0724H2UL Service Manual page 39

High static ducted type
Hide thumbs Also See for MMD-AP0724H2UL:
Table of Contents

Advertisement

How to change an indoor unit address by using a wired remote control
Use this method to change the address of indoor units (one to one or group control) that have had the original
address set automatically.
This procedure must be done while the units are not operating.
1
Simultaneously push and hold the "SET
seconds. If there are 2 or more units in a group, the first "UNIT No." indicated is the header
unit.
2
Push the left end of the "UNIT LOUVER
address to change. If 2 or more units are controlled in a group the fan and louvers of the
selected unit will be energized.
3
Push the TEMP.
4
Push the TIME
/
tion.
5
Push the "SET
" button, to save address.
SET
6
Push left and of the "UNIT LOUVER
addresses to change. Repeat steps 4 through 6 to continue changing indoor unit address and
make each of them unique.
7
Push the left end of the "UNIT LOUVER
dresses.
8
If the addresses have been changed correctly, push the "TEST
dure.
All manuals and user guides at all-guides.com
", "CL
SET
UNIT
LOUVER
/
buttons repeatedly to select
buttons repeatedly to change the value indicated in the SET DATA sec-
UNIT
LOUVER
UNIT
LOUVER
SET
DATA
SETTING
TEMP.
3
TIMER SET
5
TIME
FILTER
RESET TEST
SET CL
8
Finish
1
– 39 –
CL
", and "TEST
TEST
" button repeatedly to select an indoor unit
13 13 13 13 13
for CODE No.
" button repeatedly to select another indoor unit
" button to review/confirm the revised ad-
" button to finish the proce-
TEST
CODE No.
UNIT No.
R.C.
No.
ON / OFF
4
2, 6, 7
" buttons for more than 4

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmd-ap0964h2ul

Table of Contents