Toshiba MMD-AP0724H2UL Service Manual page 32

High static ducted type
Hide thumbs Also See for MMD-AP0724H2UL:
Table of Contents

Advertisement

Function CODE No. (DN Code) Table (Includes All Functions Needed to Perform Applied Control on Site)
DN
Item
Filter display delay timer 0000: None
01
Dirty state of filter
02
Central control address
03
Specific indoor unit
04
priority
Heating temp shift
06
Existence of [AUTO]
0d
mode
Cooling only
0F
Type
10
Indoor unit capacity
11
12 Line address
13 Indoor unit address
Group address
14
Automatic restart of
28
power failure
Selection of option/error
2A
input (CN213)
HA terminal (CN61)
2E
select
31 Ventilating fan control
32 TA sensor selection
33 Temperature unit select
Timer setting
60
(wired remote controller)
Outside interlock
92
release condition
Type
DN code "10"
Value
0006
High static Ducted
*1 Default value stored in EEPROM mounted on service P.C. board
Indoor Unit Capacity
DN code "11"
Value
Capacity
*1 Default value stored in EEPROM
0000*
Invalid
0021
072 type
0023
096 type
~
All manuals and user guides at all-guides.com
Descrip tio n
0002: 2500H
0004: 10000H
0000: Standard
0001: High degree of dirt (Half of standard time)
0001: No.1 unit
to
0099: Unfixed
0000: No priority
0000: No shift
0002: +2˚C(+3.6˚F)
to
0000: Provided
0001: Not provided (Automatic selection from connected outdoor unit)
0000: Heat pump
0001: Cool
ing only (No display of [AUTO] [HEAT])
0006: High static Ducted Type
0000: Unfixed
0001: No.1 unit
to
0001: No.1 unit
to
0000: Individual
0002: Follower unit of group
0000: None
0000: Filter input
0002: External interlock
0000: Usual
0002: Fire alarm input
0000: Unavailable
0000: Body TA sensor
0000: ˚C
0000: Available (can be performed)
0001: Unavailable (cannot be performed)
0000: Operation stop
0001: Release com munica tion signal receive
Type
MMD-AP
mounted on service P.C. board
– 32 –
0001: 150H
0003: 5000H
0064: No.64 unit
0001: Priority
0001: +1˚C(+1.8˚F)
0010: +10˚C(+18˚F)
(Up to +6 recommended)
0001 to 0034
0030: No.30 unit
0064: No.64 unit
0001: Header unit of group
0001: Restart
0001: Alarm input (Option parts)
0001: Leaving-ON prevention control 0000: Usual
0001: Available
0001: Remote controller sensor
0001: ˚F
: (at factory shipment)
Model
***
H2UL
At sh ip men t
According to type
0000: Standard
0099: Unfixed
0000: No priority
0002: +2˚C(+3.6˚F)
(Floor type 0000: 0˚C)
0001: Not provided
0000: Heat pump
According to model
type
According to capacity
type
0099: Unfixed
0099: Unfixed
0099: Unfixed
0001: Restart
0002: External interlock
(HA terminal)
0000: Unavailable
0000: Body TA sensor
0001:
:
˚F
0000: Available
0000: Operation stop