Toshiba MMD-AP0724H2UL Service Manual page 42

High static ducted type
Hide thumbs Also See for MMD-AP0724H2UL:
Table of Contents

Advertisement

Monitoring function of remote controller switch
When using the remote controller (Model Name: RBC-AMT32UL), the following monitoring
function can be utilized.
Calling of display
<Contents>
The temperature of each sensor of the remote controller, indoor unit and outdoor unit and the operating
status can be checked by calling the service monitor mode from the remote controller.
<Procedure>
1
CL
Push
+
buttons simultaneously for 4 seconds or more to call up the service monitor mode.
TEST
The service monitor goes on and firstly the temperature of the CODE No.
2
Push
button to change CODE No.
TEMP.
(CODE No.) to the CODE No. to be monitored.
For display code, refer to the following table.
3
Push
UNIT
LOUVER
button (button at left side) to change to item to be monitored.
The sensor temperature of indoor unit or outdoor unit in its refrigerant line and the operating
status are monitored.
4
Push
button to return the status to the normal display.
TEST
All manuals and user guides at all-guides.com
TEMP.
2
TIMER SET
TIME
FILTER
RESET
TEST
SET
CL
SWING/FIX
4
1
Returns to normal display
<Operation procedure>
1
2
3
– 42 –
ON / OFF
FAN
MODE
SAVE
VENT
UNIT LOUVER
3
4
00 00 00 00 00
is displayed.