Function to clear error
1. Clearing method from remote controller
How to clear error of outdoor unit
In the unit of refrigerant line connected by indoor unit of the remote controller to be operated, the error of
the outdoor unit currently detected is cleared. (Error of the indoor unit is not cleared.)
The service monitor function of the remote controller is utilized.
<Method>
1
CL
Push
+
buttons simultaneously for 4 seconds or more to change the mode to service
TEST
monitor mode.
2
Push
button to set the item code to [
TEMP.
3
The display of A part in the following figure is counted as "
0002
0002
0002
0001
0001
0001
0002
0002
0001
0001
"
" → → → → → "
" → → → → → "
0000
0000
0000
0000
0000
When "
" appear, the error was cleared.
∗ However counting from "
4
When pushing
button, the status becomes normal.
TEST
3
2
4
How to clear error of indoor unit
The error of indoor unit is cleared by
(Only error of the indoor unit connected with remote controller to be operated is cleared.)
All manuals and user guides at all-guides.com
FF
].
0000
0000
0000
0000
0000
" with 5-seconds interval.
0005
0005
0005
0005
0005
" is repeated on the display screen.
TEMP.
TIMER SET
TIME
FILTER
RESET
TEST
SET
CL
SWING/FIX
<Operation procedure>
1
2
Returns to normal status
button of the remote controller.
ON / OFF
– 41 –
0005
0005
0005
0004
0004
0004
0005
0005
0004
0004
" → → → → → "
ON / OFF
FAN
MODE
SAVE
VENT
UNIT LOUVER
1
3
4
0003
0003
0003
0003
0003
" → → → → → "
" → → → → →