Toshiba MMD-AP0724H2UL Service Manual page 64

High static ducted type
Hide thumbs Also See for MMD-AP0724H2UL:
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
controller
Check code
Sub-code
L03
L04
L04
L05
No. of priority
indoor units
L06
L06
L07
L08
L08
L09
L10
L10
L20
L28
L28
All manuals and user guides at all-guides.com
Location
of
Description
System status
detection
Indoor
Duplicated
Stop of
unit
indoor header
corresponding
unit
unit
I/F
Duplicated
All stop
outdoor line
address
I/F
Duplicated
All stop
priority indoor
unit (as
displayed on
priority indoor
unit)
I/F
Duplicated
All stop
priority indoor
unit (as
displayed on
indoor unit other
than priority
indoor unit)
Indoor
Connection of
Stop of
unit
group control
corresponding
cable to stand-
unit
alone indoor
unit
Indoor
Indoor group /
Stop of
unit
addresses not
corresponding
set
unit
Indoor
Indoor capacity
Stop of
unit
not set
corresponding
unit
I/F
Outdoor
All stop
capacity not set
Duplicated
All stop
Indoor
central control
unit
address
I/F
Too many
All stop
outdoor units
connected
– 64 –
Error detection
Check items (locations)
condition(s)
There is more than one
• Check indoor addresses.
header unit in group.
• Check for any change
made to remote controller
connection (group/
individual) since indoor
address setting.
There is duplication in line
• Check line addresses.
address setting for outdoor
units belonging to different
refrigerant piping systems.
More than one indoor unit
• Check display on priority
has been set up as priority
indoor unit.
indoor unit.
More than one indoor unit
• Check displays on priority
have been set up as priority
indoor unit and outdoor
indoor unit.
unit.
There is at least one stand-
• Check indoor addresses.
alone indoor unit to which
group control cable is
connected.
Address setting has not been
• Check indoor addresses.
performed for indoor units.
Note:
This code is displayed
when power is turned on
for the first time after
installation.
Capacity setting has not been
Set indoor capacity. (DN =
performed for indoor unit.
11)
Jumper wire provided on P.C.
Check model setting of P.C.
board for servicing I/F P.C.
board for servicing outdoor
board has not been removed
I/F P.C. board.
as required for given model.
There is duplication in central
• Check central control
control address setting.
addresses.
• Check network adaptor
P.C. board.
There are more than four
• Check No. of outdoor units
outdoor units.
connected (Only up to 4
units per system allowed).
• Check communication
lines between outdoor
units.
• Check for defect in outdoor
P.C. board (I/F).