Control Outline - Toshiba MMD-AP0724H2UL Service Manual

High static ducted type
Hide thumbs Also See for MMD-AP0724H2UL:
Table of Contents

Advertisement

No.
Item
1
When power
1) Distinction of outdoor unit
supply is reset
2) Setting of indoor fan speed and existence of air direction
3) If resetting the power supply during occurrence of a trouble,
2
Operation
1) Based on the operation mode selecting command from the
mode selection
3
Room temp.
1) Adjustment range: Remote controller setup temperature (°F [°C] )
control
Wireless type
2) Using the Item code 06, the setup temperature in heating
All manuals and user guides at all-guides.com

7. CONTROL OUTLINE

Outline of specifications
When the power supply is reset, the outdoors are
distinguished and the control is selected according to the
distinguished result.
adjustment
Based on EEPROM data, select setting of the indoor fan
speed and the existence of air direction adjustment.
the check code is once cleared. After ON/OFF button of the
remote controller was pushed and the operation was re-
sumed, if the abnormal status continues, the check code is
again displayed on the remote controller.
remote controller, the operation mode is selected.
Remote controller
command
STOP
Air conditioner stops.
FAN
Fan operation
DRY
Drying operation
COOL
Cooling operation
HEAT
Heating operation
COOL/DRY
Wired type
64°F [18°C] to 84°F [29°C]
64°F [18°C] to 86°F [30°C]
operation can be corrected.
Setup data
0
Setup temp.
+0°F
Correction
[+0°C]
Setting at shipment
Setup data
2
– 16 –
Control outline
64°F [18°C] to 84°C [29°C]
61°F [16°C] to 86°F [30°C]
2
4
6
+3.6°F
+7.2°F
+10.8°F
[+2°C]
[+4°C]
[+6°C]
Remarks
Air speed (rpm)/
Air direction adjustment
HEAT
Shift of suction
temperature in heating
operation
Except while sensor of
the remote controller is
controlled
(Code No. [32], "0001")