Toshiba MMD-AP0724H2UL Service Manual page 18

High static ducted type
Hide thumbs Also See for MMD-AP0724H2UL:
Table of Contents

Advertisement

No.
Item
5
Air speed
<HEAT>
selection
(Continued)
(–0.9) –1.8 [(–0.5) –1.0]
(+0.9) +1.8 [(+0.5) +1.0]
(+1.8) +3.6 [(+1.0) +2.0]
(+2.7) +5.4 [(+1.5) +3.0]
(+3.6) +7.2 [(+2.0) +4.0]
Value in the parentheses indicates one when thermostat of
the remote controller works.
Value without parentheses indicates one when thermostat of
the body works.
• If the air speed has been changed once, it is not changed
for 1 minute. However when the air speed exchanged, the
air speed changes.
• When heating operation has started, select an upward
slope for the air speed, that is, the high position.
• If the temperature is just on the difference boundary, the
air speed does not change.
• In TC2 ≥ 140°F[60°C], the air speed increases by 1 step.
6
Prevention of
1. In heating operation, the higher temperature of TC2 sensor
cold air
and TCJ sensor is compared with temperature of TC1
discharge
sensor and then the lower temperature is used to set the
upper limit of the fan tap.
• When B zone has continued for 6 minutes, the opera-
• In defrost time, the control point is set to +10.8°F[6°C].
˚F (˚C)
90 (32)
86 (30)
82 (28)
79 (26)
68 (20)
61 (16)
All manuals and user guides at all-guides.com
Outline of specifications
Ta ˚F (˚C)
L <L+>
L+ <H>
(0) Tsh
H <H+>
H+
<HH>
HH
<HH>
< > : Indicate automatic heating.
Body thermostat works.
Remote controller thermostat works.
tion shifts to C zone.
A zone: OFF
B zone:
D
Over 79˚F (26˚C), below 82˚F (28˚C), ULTRA LOW (LL)
C zone:
C
E
Over 82˚F (28˚C), below 86˚F (30˚C), LOW (L)
D zone:
Over 86˚F (30˚C), below 90˚F (32˚C), MED (H)
E zone: HIGH (HH)
B
A
– 18 –
Remarks
E
D
C
B
A
TC2: Indoor heat
exchanger sensor
temperature
• TCJ: Temperature of
indoor heat
exchanger sensor
• In D and E zones,
priority is given to
remote controller air
speed setup.
• In A zone "
" is dis-
played.

Advertisement