Toshiba MMD-AP0724H2UL Service Manual page 17

High static ducted type
Hide thumbs Also See for MMD-AP0724H2UL:
Table of Contents

Advertisement

No.
Item
4
Automatic
1) Based on the difference between Ta and Ts, the
capacity control
+3.6 (+2)
+1.8 (+1)
–1.8 (–1)
5
Air speed
1) Operation with (HH), (H), (L) or [AUTO] mode is carried
selection
2) When the air speed mode [AUTO] is selected, the air
<COOL>
All manuals and user guides at all-guides.com
Outline of specifications
operation capacity is determined by the outdoor unit.
COOL
Ta
˚F (˚C)
+1.8 (+1)
SD
SB
S9
S7
Ts
–1.8 (–1)
S5
S3
S0
–3.6 (–2)
out by the command from the remote controller.
speed varies by the difference between Ta and Ts.
Ta ˚F (˚C)
+5.4 (+3.0)
HH
+4.5 (+2.5)
<HH>
+3.6 (+2.0)
H+ <HH>
+2.7 (+1.5)
H <HH>
+1.8 (+1.0)
L+ <H+>
+0.9 (+0.5)
L <H>
Tsc
L <H>
–0.9 (–0.5)
L <L+>
< > : Indicate automatic cooling.
• Controlling operation in case when thermo of
remote controller works is same as a case when
thermo of the body works.
• If the air speed has been changed once, it is not
changed for 3 minutes. However when the air
volume is exchanged, the air speed changes.
• When cooling operation has started, select a
downward slope for the air speed, that is, the high
position.
• If the temperature is just on the difference bound-
ary, the air speed does not change.
– 17 –
HEAT
Ta
˚F (˚C)
S3
S0
S5
Ts
S7
S9
SB
SD
SF
HH > H+ > H > L+ > L > UL
A
B
C
D
E
F
G
Code No. 32
0000: Body thermo.
0001: Remote controller
Remarks
Ts: Setup temp.
Ta: Room temp.
(Main unit)
thermo.