I N S T A L L A T I O N O F T H E S W I T C H G E A R A T S I T E
Fig. 2.3.2.5: Distance L
to be measured
between the cast resin
busbar bushings of
adjacent panels
Fig. 2.3.2.5
Table 2.3.2.1: Specified dimensions for distance L, busbars up to 1250 A
Panel widths of the adjacent panels [mm]
450 - 450
450 - 500
500 - 450
450 - 600
600 - 450
500 - 500
500 - 600
600 - 500
450 - 600 (BT&BR)
600 (BT&BR)
600 - 600 (BT&BR)
600 (BT&BR)
600 -600
1) BusTie & Riser panel.
1)
1)
- 450
1)
- 600
1)
L
Specified dimensions for L (refer to Fig.2.3.2.5) [mm]
+2
450
-0
+2
475
-0
+2
525
-0
+2
500
-0
+2
550
-0
+2
460
-0
+2
535
-0
+2
600
-0
21