Fig. 2.3.4.5.5 Installing
the further current
transformers
Fig. 2.3.7.1 Fitting the
cover plates
Fig. 2.3.4.5.5
• Follow the same procedure to install the further
transformers.
2.3.7 Fitting the cover plates
• If the transformer is fitted with a terminal board,
wire this up as shown in the circuit diagram.
• Slide the reducer rings over the transformer leads.
During assembly of the busbar cover or pressure
relief duct, route the transformer leads through
the opening in the relevant plate behind the low
voltage compartment. The opening is sealed off
by a cover (see Fig.2.3.7.1).
Fig. 2.3.7.1
Reducer ring
Cover