ABB PrimeGear ZX0 Product Manual page 71

Gas-insulated medium voltage switchgear
Hide thumbs Also See for PrimeGear ZX0:
Table of Contents

Advertisement

T E C H N I C A L D A T A
Rated voltage
Insulating gas
Degree of protection for gas filled panel modules
Degree of protection of low voltage compartment and the mechanism bay
Ambient air temperature, maximum
Ambient air temperature, maximum 24 hour averages
Ambient air temperature, minimum
Site altitude
9)
Average humidity measured over 24 h
Average relative humidity in one month
Ambient air
6. IP 67 on request.
7. IP4X on request.
8. Higher ambient temperature on request.
9. Higher altitude on request.
10. Minimal function level operation 100 kPa on request.
11. Take suitable action to prevent condensation in the low voltage compartment.
Table 11.2: Panel weights
Panel type
Feeder panel
Feeder panel
Feeder panel (Rear Entry)
Bus Tie Panel
Bus Riser Panel
Bus Tie & Riser Panel
Disconnector Panel
6)
8)
8)
11)
11)
Panel width [mm]
450
500/600
500/600
500/600
500/600
600
500/600
DryAir /SF
7)
°C
°C
°C
m
%
%
Ambient air not significantly
contaminated by dust, smoke, corrosive
or flammable gases or salts.
Rated normal current [A]
630
1250
1250
1250
1250
1250
1250
71
12 kV
24 kV
AirPlus/SF
6
6
IP65
IP3X
+40
+35
-15
...1000
≤95
≤90
Weight, max. [kg]
650
800
1000
900
700
1400
800

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents