ABB PrimeGear ZX0 Product Manual page 6

Gas-insulated medium voltage switchgear
Hide thumbs Also See for PrimeGear ZX0:
Table of Contents

Advertisement

6
P rimeGe ar Z X0 P R O D U C T M A N U A L
IAC
Operator safety in accordance with IEC 62271-200
| GB 3906 assumes that the conditions stipulated
by ABB are complied with (see also Technical
Catalogue TK 1YHA000299).
The IAC qualification relies on a system consisting
of at least two panels.
You have chosen a gas-insulated switchgear of
series PrimeGear ZX0. This switchgear is notable
for the following features:
• Gas-insulated with hermetically sealed pressure
systems.
• Solid insulated busbar.
• Rated voltages up to 24 kV.
• Up to 1250 A and 25 kA.
• Single busbar design.
• Stainless steel encapsulations, manufactured
from laser cut sheet steel.
• Modular structure.
• Switchgear with a leakage rate of less than 0.1 %
per year.
• Integrated routine leakage testing of the panels
ex-works.
• Indoor installation.
AFLR
31.5 kA
1 sec
The operator of the switchgear must
prevent access by personnel to non-arc
classified areas, for instance by issuing
instructions.
Within the ratings stated on the name
plate, the switchgear is safe for
operating personnel in accordance with
IEC 62271-200 | GB 3906 when all system
components are completely and properly
installed.
Commissioning, servicing and extension
work require special attention with regard
to safety (see also IEC 62271-200 | GB 3906).
Duration of fault current
Level of fault current
Successfully tested accessibility of the area behind the switchgear
(R - rear)
Successfully tested accessibility of the area to the side of the
switchgear (L - lateral)
Successfully tested accessibility of the area in front of the
switchgear (F- front)
Switchgear installed in closed rooms with access restricted to
authorized personnel
Internal arc classification
• Wall mounting installation and free-standing
installation.
• Operator controls separate from low voltage
compartment.
• Operator controls on the panel accessible from
the outside.
Please observe further documents in addition to
this manual. The documents relevant to your
switchgear are part of the final documentation.
Installation checklist
Order documents
• Single line diagram.
• Front view.
• Construction data if compiled specifically for
this order.
• Circuit diagrams.
• Earthing diagram – switchgear earth to station
earth (not part of ABB supply).
Instruction manuals
• Use of Air
• Use of AirPlus
• Use of SF
• Circuit breaker VD4X0
• Material supplement
Operating instructions and directions for
components, e.g.
• Surge arresters.
• Current and voltage transformers.
• Current and voltage sensors.
• Protection and control devices.
• Capacitive indicators.
• Solid insulated busbar.
• VT cable.
1YHA000330
1YHA000334
1YHA000300
insulating gas
1YHA000333
6
1YHA000331
BA 509