Programming The Xls-Rel In The Xls1000-Sdu (Revision 1.5); Adding The Xls-Rel To The Database - Honeywell XLS-REL Technical Reference Manual

Releasing module
Table of Contents

Advertisement

Programming the XLS-REL

Programming the XLS-REL in the XLS1000-SDU (Revision 1.5)

Break Chain button
2.6

Adding the XLS-REL to the database

Warning! This information was prepared for users who are
proficient in every aspect of XLS1000-SDU (Revision 1.5)
programming. DO NOT attempt to program the XLS-REL if your
certification is not current. Failure to do this may result in loss of
life, serious injury, or property damage.
Caution! If you are adding other Signature Series devices to the
project database, add the XLS-REL last. Adding devices after the
XLS-REL may disrupt the addressing scheme. The XLS-REL is a
single module with six serial numbers, but the XLS1000-SDU
(Revision 1.5) recognizes it as three SIGA-UMs. Addresses will
differ for each installation, but they must be consecutive.
The XLS-REL provides only one serial number label. When you
scan in the XLS-REL, only the first two serial numbers will
appear in the database.
To add the XLS-REL to the database:
1
Scan in the XLS-REL serial number label.
2
In the DSDC configuration (Loop X Modules tab), ensure
that four blank addresses follow the first two addresses.
3
Add two more SIGA-UMs (four address spaces) to the
database to fill in the four empty addresses.
4
In the Signature Series mapping tool, access the Actual vs.
Expected Data dialog box (F9 key).
5
Click Break Chain and select the appropriate address.
6
Commit the expected data.
7
In the DSDC configuration, configure the XLS-REL
(SIGA-UM) addresses in strict accordance with Tables 2-4
and 2-5.
XLS-REL Technical Reference Manual