[ALARM1]
ALARM 'ALARM_1' : ON 'PRERELEASE_1';
[ALARM2]
ALARM 'ALARM_2' : ON 'PRERELEASE_1';
[RELEASE]
DEFINE AND 'AND_GROUP1' : DELAY 10,
[RESET]
DEFINE SYSRESET 'MCMN1' : OFF 'PRERELEASE_1',
[DUMP]
ALARM 'MANUAL' : ON 'RELEASE_1';
Figure 2-1: Mandatory rules of the XLS-REL
[DRILL]
DEFINE DRILL 'MCMN1' : ON 'PRERELEASE_1';
[LED1]
CONFIRMATION 'PRERELEASE_1' :
[LED2]
CONFIRMATION 'RELEASE_1' :
Figure 2-2: Optional rules for the XLS-REL
XLS-REL Technical Reference Manual
Note: See the system testing section, at the end of this chapter,
before you test of your system.
Note: [ALARM_1] and [ALARM_2] require the
addition of two Signature Series alarm devices to
the SDC Configuration. Make sure that the object
labels in the rules match the labels assigned in
the Object Configuration.
ON 'RELEASE_1';
OFF 'RELEASE_1';
Note: [LED1] and [LED2] require the addition of
an LED module to the MCM Configuration. Make
sure that the labels for the LEDs match the labels
assigned to them in the Object Configuration.
ON 'LED_1_1';
ON 'LED_1_2';
Avoid using the Drill switch to test the XLS-REL. If you activate
a Drill, press the Reset switch to deactivate it. The deactivation of
the Drill switch, alone, will not silence the prerelease tones.
Programming the XLS-REL
RELEASE010.CDR
RELEASE032.CDR