Specifications - Honeywell XLS-REL Technical Reference Manual

Releasing module
Table of Contents

Advertisement

Specifications

Power riser
Input voltage
Supervisory current
Alarm current
Line resistance
Release circuits, TB4
Output (release circuit 1)
Output (release circuit 2)
Valves per circuit
Line resistance
End of line device
Prerelease circuits, TB5
Output (prerelease circuit 1)
Output (prerelease circuit 2)
Line resistance
End of line device
Manual release input circuit, TB3-1 and TB3-2
Line resistance
End of line device
Circuit capacitance
Abort circuit, TB3-3 and TB3-4
Line resistance
End of line device
Circuit capacitance
First alarm contact, TB2
Contact rating
Signature Data line, TB1
Operating voltage
Supervisory current
Alarm current
Line resistance
Maximum quantity
XLS-REL Technical Reference Manual
*Riser current:
Total current of output circuits is limited to the
power riser input current (up to 4 amps) minus 170 mA.
24 Vdc
25 mA, max.
170 mA min., 4 A max.
(depends on output circuit loading)
See Table 1-5.
2 A @ 24 Vdc, max. (*See riser current.) TB4-1 and TB4-2
2 A @ 24 Vdc, max. (*See riser current.) TB4-3 and TB4-4
4 valves, max.
See Table 1-6.
47 kW resistor
2 A @ 24 Vdc, max. (*See riser current.) TB5-1 and TB5-2
2 A @ 24 Vdc, max. (*See riser current.) TB5-3 and TB5-4
See Table 1-6.
47 kW resistor
25 W/wire, #18 AWG = 3800 ft (0.75 mm
47 kW resistor
0.1 mF, max.
25 W/wire, #18 AWG = 3800 ft (0.75 mm
47 kW resistor
0.1 mF, max.
3 A @ 24 Vdc, (resistive load) Form C
15.2 to 19.95 Vdc
1 mA
1 mA
See the installation sheet of the Signature loop controller.
Ten XLS-RELs per loop
Installing the XLS-REL
2
= 1158 m)
2
= 1158 m)
1.7