Installing the XLS-REL
Environmental conditions
Operating temperature
Storage temperature
Humidity
Table 1-5: Power riser
Total riser
current
(Amps)
#12 AWG
4.0
29 ft
3.5
34 ft
3.0
39 ft
2.5
47 ft
2.0
59 ft
1.5
78 ft
1.0
118 ft
Table 1-6: Prerelease and release circuits (per circuit)
Total riser
current
(Amps)
#12 AWG
2.00
176 ft
1.75
202 ft
1.50
235 ft
1.25
282 ft
1.00
353 ft
0.50
706 ft
1.8
32 to 120 °F (0 to 49 °C)
-4 to 140 °F (-20 to 60 °C)
0 to 93% RH, non-condensing
Distance from XLS-REL to power supply
#14 AWG
2
2.5 mm
8.84 m
10.36 m
11.89 m
14.33 m
17.98 m
23.77 m
35.97 m
Distance from XLS-REL to signals
#14 AWG
2
2.5 mm
53.64 m
61.57 m
71.63 m
85.95 m
107.59 m
215.19 m
2
1.5 mm
20 ft
6.10 m
23 ft
7.01 m
27 ft
8.23 m
32 ft
9.75 m
40 ft
12.19 m
53 ft
16.15 m
80 ft
24.38 m
2
1.5 mm
120 ft
36.58 m
137 ft
41.76 m
160 ft
48.77 m
192 ft
58.52 m
240 ft
73.15 m
480 ft
146.30 m
XLS-REL Technical Reference Manual
Wire
resistance
(W per wire)
0.050
0.057
0.067
0.080
0.100
0.133
0.200
Wire
resistance
(W per wire)
0.300
0.343
0.400
0.480
0.600
1.200