Automatic Fire Extinguishing Systems - Honeywell XLS-REL Technical Reference Manual

Releasing module
Table of Contents

Advertisement

Installing the XLS-REL
Table 1-3: FM approval requirements for automatic fire extinguishing systems
Specification
Standby operation
Alarm operation
NFPA style
FMRC documentation
1.4

Automatic fire extinguishing systems

Warning! Improper applications of fire suppression agents can
lead to property damage, injury, or loss of life. Consult the
applicable NFPA documents and the authority having jurisdiction
(AHJ) for more information.
Automatic fire extinguishing systems automatically detect and
extinguish fires. They require no manual input because detectors
automatically activate releasing solenoids or sprinkler valves.
Table 1-2 provides a list of the fire suppression agents and the
applicable NFPA documents.
Table 1-2: Fire suppression agents and NFPA documentation
Agent
Low-expansion foam
Medium- and high-expansion foam
Sprinklers
Water spray
Foam-water
Dry chemicals
Warning! The XLS-REL is not listed for use with CO
suppression systems.
Table 1-3 outlines the FMRC requirements for automatic fire
extinguishing systems.
Value
24 hours
10 minutes
B or D
FMRC Approval Guide (Volume 1)
NFPA documentation
NFPA 11
NFPA 11A
NFPA 13
NFPA 15
NFPA 16
NFPA 17
XLS-REL Technical Reference Manual
or Halon
2