Typical Display Of Mr Series Actuators; List Of Programming Menus; Password; Select Language - Honeywell VPI Series Installation Instruction

Pressure independent control valves and actuators
Table of Contents

Advertisement

VPI Pressure Independent Control Valves & Actuators
Configuration and Setup
Start-Up Sequence
When power is turned on, the actuator will automatically calibrate to determine the closing point of the valve.
Calibration can take up to 10 minutes depending on the valve's position at start-up. During the calibration actuator,
the display will show "CAL". Hereafter it will proceed to the normal operation mode (according to control signal).
If no control signal is detected, flush is started if enabled in the programming menu (enabled by default), opening the
valve to 5/6 of fully open. Actuator display will show "FLUSH" until control signal is detected.
At first start-up please enter programming menu to set actuator settings.
Programming Menu
The programming menu is always accessible. To enter the programming menu, simultaneously press  and  for 6
seconds, until the bottom line in display blinks.
To change a value, press
to the next step and press
For fast menu exit press
operation mode if no action is detected on arrow keys for 1 minute.
NOTE- All values selected in the programming menu are stored in non-volatile memory
Step
Display
0
1
2
31-00383-01
Figure 19. Typical display of MR series actuators
, or
. For quick scroll through values hold down
to go to the previous step.
and
simultaneously for 6 seconds. The actuator will automatically return to normal
Table 6. List of Programming menus
Description

Password

.
scrolling top: ENTER PASSWORD
*

Select language

*scrolling top: SELECT LANGUAGE
Select valve model onto which the
actuator is installed.
*scrolling top: SELECT VALVE MODEL
or
Disabled by default Password: 3569266.
Only if Enabled (in step 12).
Change one digit at a time, press
between digits.
At last digit, press
Default: English.
Default: 50H.
Select from the 12 available valve models.
Options: 50H, 65H, 80L ... See, Table 5. List of
Reference Valve Codes for more options.
18
. Press
to accept a value and go
Valve
and to move
to go to next step