Honeywell XLS-REL Technical Reference Manual page 31

Releasing module
Table of Contents

Advertisement

Table 2-4: Device type selections
Typical address
Typical serial number
126*
5300411525*
127*
5300411532*
128
5300411549*
129*
5300411556*
130*
5300411563*
131*
5300411570*
XLS-REL Technical Reference Manual
Caution! Do not use the Accept Actual function in the Signature
Mapping tool. Accepted data may corrupt the database by causing
it to see every device as two devices.
Warning! DO NOT configure the third and fifth SIGA-UM
addresses as common outputs or audio amplifiers. Any off-
normal condition will activate the automatic release sequence if
these addresses are common outputs. The Drill switch will
activate the prerelease and the release circuits if they are audio
amplifiers. You must select the device types and personality
codes exactly as prescribed in Tables 2-4 and 2-5.
Device type
Monitor
Pull
SupervisedOutput
None
SupervisedOutput
None
Table 2-5: Device type personality codes
Typical address
Personality code
126*
3
127*
1
128*
16
129*
0
130*
16
131*
0
*Actual addresses in your system may differ, but they must be
consecutive. Serial numbers must also be consecutive up to the
second-to-last digit.
Programming the XLS-REL
Model
SIGA-UM
SIGA-UM
SIGA-UM
SIGA-UM
SIGA-UM
SIGA-UM
N/O Active - Non-Latching (Class B)
N/O Alarm Latching (Class B)
Signal Output (Class B)
No personality
Signal Output (Class B)
No personality
2.7