Programming the XLS-REL
Table 2-3: XLS-REL labels
Device Type
Typical address
Monitor
0207*
Pull
0208*
DoorControl
0209*
None
0210*
DoorControl
0211*
None
0212*
2.4

Labeling the XLS-REL components

In the Object Configuration, assign the labels and messages listed
in Table 2-3 to the SIGA-UM.
Label
Abort
Manual
Release_1
Release_2
Prerelease_1
Prerelease_2
*The addresses in Table 2-3 demonstrate the importance of
ensuring that the XLS-REL occupies six consecutive addresses.
The actual addresses in your system may differ.

Programming an AND group

AND groups function as cross zones. For more information about
programming AND groups, see the XLS100 System Programming
Manual and the XLS100-SDU Help.
Note: Every device contained in each (XLS-REL) AND group
must include a rule with an output statement like the one in
[ALARM1]. See Figure 2-1 for the details.

Reconciling the Signature map

Caution! Do not use Accept Actual in the Signature Series
mapping tool. Accepted devices may appear as two devices in the
SDC database and corrupt it. Use the Break Chain and Commit
Expected functions to reconcile the Signature map.

Writing rules for the XLS-REL

To write the rules:
1
In the Rules Editor, write the mandatory rules in Figure 2-1
and the optional rules in Figure 2-2.
2
Compile the rules and run the required conversions.
3
Download and upload the new information.