[ALARM1]
ALARM 'ALARM_1' :
[ALARM2]
ALARM 'ALARM_2' :
[ANDGROUP DUMP]
ALARM 'AND_GROUP1' :
[DUMP]
ALARM 'MANUAL' : ON -HIGH 'RELEASE_1';
Figure 2-3: Mandatory rules for the XLS-REL
[DRILL]
DRILL :
ON 'PRERELEASE_1';
[LED1]
RLYCFG 'PRERELEASE_1' :
[LED2]
RLYCFG 'RELEASE_1' :
Figure 2-4: Optional rules for the XLS-REL
XLS-REL Technical Reference Manual

Reconciling the Signature map

Caution! Do not use Accept Actual in the Signature Series
mapping tool. Accepted devices may appear as two devices in the
SDC database and corrupt it. Use the Break Chain and Commit
Expected functions to reconcile the Signature map.

Writing rules for the XLS-REL

To write the rules:
1
In the Rules Editor, write the mandatory rules in Figure 2-3
and the optional rules in Figure 2-4.
2
Compile the rules and run the required conversions.
3
Download and upload the new information.
Note: See the system testing section, at the end of this chapter,
before you test of your system.
ON 'PRERELEASE_1';
ON 'PRERELEASE_1';
DLYA 10,
ON 'RELEASE_1',
DLYR 10;
Note: [LED1] and [LED2] require the addition of an LED
module to the Cabinet Configuration (Modules tab,
operator layer). Make sure that the labels for the LEDs
match the labels assigned to them in the Object
ON 'LED_1_1';
Configuration.
ON 'LED_1_2';
Avoid using the Drill switch to test the XLS-REL. If you activate
a Drill, press the Reset switch before you deactivate it. The
deactivation of the Drill switch, alone, will not silence the
prerelease tones.
Programming the XLS-REL
Note: [ALARM_1] and [ALARM_2] require the addition
of alarm devices to the panel configuration. Make sure
that the object labels match the labels assigned to
them in the Object Configuration.
RELEASE011.CDR
RELEASE033.CDR
2.9