Honeywell NOTIFIER XP6-MA Installation And Maintenance Instructions

Six zone interface module

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
XP6-MA Six Zone Interface Module
SPECIFICATIONS
Normal Operating Voltage:
Stand-By Current:
Alarm Current:
Temperature Range:
Humidity:
Dimensions:
Accessories:
Wire Gauge:
Maximum IDC Wiring Resistance:
External Power Supply Voltage:
Ripple Voltage:
IDC (supervised and power limited)
DC Voltage:
Frequency:
Alarm Current:
Standby Current 6 circuits:
BEFORE INSTALLING
If the modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the modules. This
system contains static sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The module housing should also be grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The XP6-MA Six Zone Interface Module is intended for use in an intelligent
alarm system. Each module provides an interface between the intelligent
alarm system and a conventional alarm system loop. A common SLC input is
used for all modules, and the initiating device loops share a common super-
visory supply and ground. Otherwise, each monitor operates independently
from the others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the first module
from 01 to 154. The remaining modules are automatically assigned to the next
five higher addresses. Provisions are included for disabling a maximum of two
unused modules to release the addresses to be used elsewhere. Each mod-
ule also has panel controlled bicolor LED indicators. The panel can cause the
LEDs to blink, latch on, or latch off.
A list of compatible two-wire System Sensor Smoke detectors for use with the
XP6-MA is available on the System Sensor website at www.systemsensor.com.
Included:
(5) 1 x 4 Terminal Blocks
(2) 1.25" Stand offs
(4) Machine Screws
(2) Nuts
(6) 3.9k Ohm End of Line Resistors
Shipped on Board:
(2) Shunts in Class A/B position
(Shipped in Class B position, remove shunts for Class A)
15-32VDC
2.3 mA @ 24 V
40 mA (assumes all six LEDs solid on)
32ºF to 120ºF ( 0ºC to 49ºC)
10 to 93% Non-condensing
6.8˝H x 5.8˝W x 1.25˝D
CHS-6 Chassis; BB-25 Cabinet; BB-XP Cabinet; CAB-4 Series Cabinets; CAB-3 Series Cabinets
12-18 AWG
25 Ohms
Regulated 24 VDC
0.1 volts RMS maximum
18-28 volts power limited
DC
90mA per circuit
42mA Maximum @18 VDC
56mA Maximum @24 VDC
66mA Maximum @28 VDC
(3) Shunts
(1) Long Power Supply Jumper
C0202-00
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Notifier system control panel (list available from Notifier).
COMPONENTS
Following are descriptions of the XP6-MA mounting frameworks. There are
two mounting options for XP6-MA modules:
• Up to six XP6-MA modules can be installed on a CHS-6 in a CAB-3
Series, CAB-4 Series or BB-25 cabinet
• One or two XP6-MA modules can be installed in a BB-XP cabinet
Chassis
The CHS-6 chassis is used to mount XP6-MA modules in a BB-25, CAB-3 or
CAB-4 Series cabinet. It accommodates up to six XP6-MA modules in a single
cabinet row three modules wide and two modules deep.
FIGURE 1. CHS-6 CHASSIS
The BB-XP cabinet has a built-in chassis that will accommodate one or two
XP6-MA modules.
FIGURE 2. BB-XP CABINET
1
12 Clintonville Road
Northford, CT 06472-1653
Phone: 203.484.7161
MOUNT WITH
SELF-THREADING SCREWS
TO BACK OF CABINET
I56-1806-010
C0236-01
C0234-00
7/1/2022

Advertisement

loading

Summary of Contents for Honeywell NOTIFIER XP6-MA

  • Page 1 INSTALLATION AND MAINTENANCE INSTRUCTIONS 12 Clintonville Road XP6-MA Six Zone Interface Module Northford, CT 06472-1653 Phone: 203.484.7161 SPECIFICATIONS Normal Operating Voltage: 15-32VDC Stand-By Current: 2.3 mA @ 24 V Alarm Current: 40 mA (assumes all six LEDs solid on) Temperature Range: 32ºF to 120ºF ( 0ºC to 49ºC) Humidity: 10 to 93% Non-condensing...
  • Page 2 The front XP6-MA module positions of each chassis are offset below the rear The steps in Figures 6A – 6C describe and illustrate module installation when XP6-MA module positions so that all of the status indicators are visible. the rear chassis position and the position in front of it will be filled. Front position installation is possible only if the rear position is filled with an XP Cabinets module.
  • Page 3 from the end of wire, sliding the bare end of the wire under the clamping NOTE: Power must not be applied to the unit when changing functionality on plate screw. the shunts. WIRING NOTES Set the address on the modules per the job drawing. Use the rotary code •...
  • Page 4 – Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. – Consult the dealer or an experienced radio/TV technician for help. NOTIFIER is a registered trademark of Honeywell International, Inc. ® I56-1806-010...