Purge; Emergency Stop In The Event Of Fire Or Electric Shock; Emergency Stop Triggered By Safety Interlock; Overload Protection - Honeywell krom schroeder IFD 258 Manual

Automatic burner control unit
Table of Contents

Advertisement

7 .3 Purge

In the case of multiple burner applications, burners
with forced air supply are used. The air for combustion
and pre-purge is supplied by a central fan controlled
by a separate logic. This logic determines the purging
time and controls an external relay that switches the air
valve to purge.
The automatic burner control unit must not be activat-
ed during purging. This is achieved by interrupting the
safety interlock, amongst other methods.
10
11
GIK..B
VAS
VR..R
7 .4 Emergency stop in the event of fire or
electric shock
If there is a risk of fire, electric shock or similar, inputs
L1, N and 3 (start-up/safety interlock signal) of the IFD
IFD 258 · Edition 03.12l
13
14
5
Purge
BIO/
BIC
N
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวี ว ั ฒ นา กทม. 10170.
website:
https://www.add-furnace.com/
Line ID: @add11 e-mail: add028883472@gmail.com
should be disconnected from the electrical power sup-
ply.
Important! This should be reflected in the wiring on
site!
7 .5 Emergency stop triggered by safety
interlock
The safety interlock turns off the power to the input 3
(start-up/safety interlock signal), such as in the event of
air deficiency or similar.

7 .6 Overload protection

To protect the unit against overload by frequent cycling,
only a specific number of start-up attempts can be car-
ried out by the IFD. The maximum number of start-up
attempts per minute depends on the safety time t
and the ignition unit.
t
t
SA
Z
[s]
[s]
3
1.8
5
3
10
6
3
1.8
5
3
10
6
If too many start-up attempts are made,
the display to indicate a fault.
โทร: 02-888-3472
SA
Type of ignition
Cycle lock
[s]
External TZI
10
External TZI
12
External TZI
15
IFD..I
36
IFD..I
60
IFD..I
120
flashes on
28