System Data Menu 6B Program - B. Braun Aquaboss CCS Instructions For Use Manual

Table of Contents

Advertisement

CCS
8.8.2

System data menu 6B Program

6 System data
Enter code
XXXX
Esc
+
-
6.1
Concentrate 1.1
Press.val. = X.XXbar
rpm min=XX
Esc
+
-
6.8
Routine check
XX months
Esc
6.9
Hours system
XXXXXX hours
Esc
6.10
Economy mode
SV 11 12 21 22 31 32
X
X
X
Esc
6.11 Remote - on/off
XXXXXXXX
Esc
6.12 Control param.
Line X.X
Kp=X.X
Ki=XXXms
Esc
Page 8-6
System data parameters
Section 1 – Operating Instructions
When menu 6.B Program is selected, the following screen appears:
A 4-digit service code must be entered for the system data to be
changed.
Enter
Menu 6.1B to 6.6B
Pressure 0.10 to 5.00 bar (D = 0.05 bar).
rpm min Minimum speed = 0 to 99 % (D = 1 %).
max=XXX %
Enter
rpm max Maximum speed = 10 to 100 % (D = 1 %).
Input range 1.1 / 1.2 / 2.1 / 2.2 / 3.1 / 3.2.
Service interval
Input range: 0 to 12 months (0 = -- = off).
System hours
Reset = Reset of system hours to 0.
Reset
Economy mode
Each individual valve can go into economy mode to save energy during
the holding phase and to prevent local valve warming.
X
X
X
Economy mode solenoids on/off / input range 0/1
Remote control remote on/off
Input possibilities:
Pulse trigger / slope trigger.
(Positive slope means system on; negative slope = system off.)
Control parameters
To adjust the control parameters of every concentrate line (1.1 – 3.2)
Enter next number
Kp Proportional amplification 0.1 to 1.0 (D = 0.1).
Ki Integration time constant 20 to 980 ms (D = 20).
Rev. 2.8 Date 2019-02-04
Software version 1.00

Advertisement

Table of Contents
loading

Table of Contents